20 Most Recent Amana DigiSmart PTH153B35AM Thru-Wall/Window Air Conditioner - Page 3 Questions & Answers

0helpful
1answer

Amana Model HKR10A. heat doesn't work. Replaced the heat element. Still no heat. Fan comes on but blows cold air. Voltage to unit seems ok. What else can it be? A/C works fine.

I would guess two possible problems - dirty thermostat contacts and many appliances are also fitted with a thermal fuse or other type of thermal cutout which might have failed.
12/13/2018 2:19:17 AM • Amana Heating &... • Answered on Dec 13, 2018
0helpful
1answer

Can someone tell me how to fix the heating coil on my amana ptac?

How much power is the question. Remember, heating coils usually require 240 volts. You likely are only getting 115 due to a faulty limit switch. 115 will carry through to the other side of the switch from the coil side leading you to believe the switch is good. Remove both sides of switch and test continuity.
12/12/2018 12:33:59 AM • Amana Heating &... • Answered on Dec 12, 2018
0helpful
1answer

Hi I'm Steve... Amana SSE80 Furnace Model GUIC070CA40 MFG # P1229003F Furnace works but air handler blower stops after 5 1/2 minutes, burner continues till high-T limiter triggered (See details)

Motor might be bad and shutting down on thermal protection. Is this a direct drive or belt driven ? .if belt driven try adjusting the belt tension or just replaced the motor
12/11/2018 11:22:45 AM • Amana Heating &... • Answered on Dec 11, 2018
0helpful
2answers

Amana ptac evap fan does not come on. how do I trouble shoot it?

What turns on the fan, a relay of its own, a defrost board, the compressor contractor? Check for power before and after the contacts. Read the lone or schematic diagram included with the unit if possible.
11/1/2018 1:19:39 PM • Amana Heating &... • Answered on Nov 01, 2018
0helpful
1answer

Large blower on Amana 80 SSE wont go on. Small fan goes on and burner is lit.

It will be one of three issues. Blower motor is bad , capicator, or the control board. Easy enough to check . Use an extension cord , cut off the female end and strip it . You should have a black and white wire. Find the wires leading to the motor take the black and white off the control board conect black to black and white to white. Plug it in an outlet if the motor runs its the control board . If not its a bad motor or capicator. But caps rarely go bad in this use . So most likely motor . Not a hard job , but not eady if you dont have the right tools. Do not bang on the shaft with a hammer . You must use a special tool for pulling shafts.
9/30/2018 11:43:57 PM • Amana Heating &... • Answered on Sep 30, 2018
0helpful
2answers

My AMANA PTAC unit model # PTH093b35ae is not producing heat. My air conditioner works fine. So, I get cold air. However, when I switch to heat, it still runs but does not produce any heat.

It is not switching from cooling into heating. You probably need to have a service tech look at the unit. Sorry. It could be control board or stuck reversing valve.
9/26/2018 5:09:31 PM • Amana Heating &... • Answered on Sep 26, 2018
0helpful
2answers

When I try to plugin My Amana ptac it blow breaker .What could be the reason.

You have a shorted unit. Check the compressors, condensing motors, and the indoor fan motor. Replace defective parts found from the unit.
9/26/2018 4:58:04 PM • Amana Heating &... • Answered on Sep 26, 2018
0helpful
1answer
0helpful
1answer
0helpful
1answer

I have a amana ptac unit that only runs at low speed even when high is pressed please help

It could be the motor speed windings are bad for higher speed or switch/controller needs to be replaced
8/22/2018 4:44:17 PM • Amana Heating &... • Answered on Aug 22, 2018
0helpful
1answer
0helpful
1answer

Westinghouse air conditioner P4

I have a P4 code in a inverter white westinghouse 24000btu air
8/21/2018 4:43:26 AM • Amana Heating &... • Answered on Aug 21, 2018
0helpful
1answer

Air intake via hose & window or intake from room only?

Hello artrey3 The answer is yes, BUT the unit will be exausting room/basement air outside ruining any efficency the unit is rated for.Also you will need makeup/fresh air in the basement. The unit exausting air can put the basement in a vacuum/negitive pressure pulling in air from the chimney!
7/26/2018 12:35:12 PM • Amana Heating &... • Answered on Jul 26, 2018
0helpful
1answer

Model Amana AP095R - does the water drainage have to be dumped everyday?

There is no right answer to that It gets dumped when its full. The more water the better, the more water the harder its working, the more water the more dehumidification. More water is a good thing, run a permanent drain if need be.
7/2/2018 10:13:04 PM • Amana Heating &... • Answered on Jul 02, 2018
0helpful
2answers

Amana portable air conditioner leaking water 14000 btu

they are not filled with water thats the condensation that it is making, its all good, keep the temp at a steady rate, when you get it ice cold then shut her down it makes moisture which then is water.
7/2/2018 6:06:44 PM • Amana Heating &... • Answered on Jul 02, 2018
Not finding what you are looking for?
Amana DigiSmart PTH153B35AM Thru-Wall/Window Air Conditioner Logo

9 questions posted

Ask a Question

Usually answered in minutes!

Top Amana Heating & Cooling Experts

Mike Cairns
Mike Cairns

Level 3 Expert

3054 Answers

Jay Finke
Jay Finke

Level 3 Expert

1397 Answers

Cindy Wells

Level 3 Expert

6688 Answers

Are you an Amana Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions