H3 is compressor overload protection. This occurs either during very high load environments (very high outdoor temps and direct sunlight on unit) or when the compressor or compressor start components fail.
You can reset the indoor and outdoor breakers to clear the code and try the system again. If it fails again and the outdoor temp isnt overly excessive, then it is likely a compressor issue and not really a DIY project at this point, since you will be dealing with refrigerant.