The heating has been fine for two years - then the boiler would not ignite if both the hot water and the central heating were to come on together, they both work fine individually. I had a plumber look at the boiler and he said the boiler was fine but I needed a new programmer. I have replaced the programmer with the same model, as i was told I could leave the back plate on - and still it does not work - any ideas
What size of gas line is going into boiler and water heater? is it black iron ? natural gas or propane? have you checked gas pressure at water heater and furnace ? if they work fine individually then you have a problem with incoming gas pressure. Call gas company and ask them if they would come out and check gas pressure.
680 views
Usually answered in minutes!
hi could you give me boiler details make/model and programmer model/make , it sound like there is a link missing in the boiler control panel ? or programmer base is wired incorrect ? some have links in which need moving or not ?
×