D25 code : Check power supply voltage to the outdoor unit is correct (1ph ?220 Vac ±10% or 3ph ?380 Vac ±10%). If OK, check fuses, if fuses are OK replace outdoor main PCB
D26:
compressor seized. Check compressor windings all equal resistance 1 to 4 Ohms, check to earth 50 MOhm minimum, check run current and Inverter outputs
Hope helpful?
298 views
Usually answered in minutes!
This is for a Multi Split Air Conditioner SAP-CMRV3143GJH
×