When compressor on the blower keeps trying to shut down.

My goodman central air is cooling the house but when the compressor shuts off the blower will pulse off&on (blowing warm outside air in; as if it wants to come on).When it is time for it to cool again the compressor will run fine but the blower will keep trying to shut off.It will blow enough to cool the house but it aint right.what can I check for?

Posted by on

Ad

2 Answers

  • Level 1:

    An expert who has achieved level 1.

  • Contributor
  • 1 Answer

My air conditiong comes on and than shuts off the air is cool there is a hissing sound comming from the indoor unit

Posted on Jul 18, 2009

Ad
  • Level 3:

    An expert who has achieved level 3 by getting 1000 points

    All-Star:

    An expert that got 10 achievements.

    MVP:

    An expert that got 5 achievements.

    Vice President:

    An expert whose answer got voted for 100 times.

  • Master
  • 614 Answers

You may have a bad capacitor. But you may nee a service tech to check it out. There is only so far you can go without knowledge of Air Conditioning. Ask for free estimate and you will know upfront what the cost is . RUS

Posted on Jul 15, 2009

Ad

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

When house cools furnace blower shuts off but ac unit fan does not shut off


the relay inside the condenser outside has pitted contacts an is likely stuck.
its 220 an you have to know what your doing
its not too expensive an easy to test
the contact might even be able to be ground down a tad to make new contact area .

Sep 12, 2015 | Goodman Heating & Cooling

2 Answers

Condencer runs for 20 sec then off keeps repeting after 2 or 3 min goodman central system


Seems like it trying to start and then cuts out , possibly on overload. Try the machine on fan blow only , that will check the indoor unit to see if that is working. Then try cool or heat function while listening to the machine starting. If you hear a loud humming just as the fan starts, and then it cuts out, It could be a compressor issue. Possibly the start capacitor has failed.

May 27, 2015 | Goodman Heating & Cooling

1 Answer

Central heating&cooling


sounds like your compressor is getting hot and shutting down have you washed your outside condenser coil? Could be dirty causeing high head pressure and shuts your compressor down. Try washing your condenser coil I think this will help you. If not you may be low on charge of Freon.

Aug 17, 2014 | Rheem 13AJN30A01 Central Air Conditioner

1 Answer

Ac unit runs, inside blower shuts off after 2 mins, compressor continues to run, t-stat still calling for cool


My central AC unit decided to stop on the hottest day of the year. It would start and run normally for a few minutes and then the blower would shut off. After checking the breakers, thermostat and overflow shut off (did not have one) I saw something about a blower motor capacitor. This was easy to get to and replace and my last hope before waiting for someone to come fix it. The capacitor cost $4.04 with tax and had my AC working again. Needless to say I was beyond happy. I hope this can help others with a similar problem.

May 20, 2012 | Heating & Cooling

1 Answer

Hello, we had central air conditioner installed last October. We turned our unit on for the first time and the outside unit shuts down but the air handler continues to blow air and never shuts down. ...


Hello, if the blower motor runs continuously and does not shut off at tne thermostat then the relay on tne integrated control board is bad. Only option is to replace the control board

Jun 28, 2011 | Goodman CKL36AR36 Air Conditioner

1 Answer

My furnace heats the house well, but during the cool down it actually blows cold air dropping the temperature causing the furnace to re-ignite. How do I adjust? Goodman - GMS9/GCS9


Depending on the age of the furnace you may be able to adjust the cool down. On some furnaces there is a silver box usually made by honeywell. This is your fan limit control. If you take the cover off you will see a dial with different temperature settings with 3 pins in a grove. The first one is fan on with temperature rise this turns the blower on when the furnace starts and warms up. The second is the fan off after furnace shuts down, this would be the one you want to adjust to a higher temperature to keep the blower from blowing cold air. The last pin is the high limit if the furnace gets to this temperature it will shut the furnace off but keep the blower running. Make sure that the thermostat fan option is set to auto and not on.

Jan 02, 2010 | Goodman GMS90703BXA Heater

1 Answer

Compressor runs 45 seconds off for 2 minutes cycles like this no voltage change


In order to accurately determine and diagnose the problem, a more detailed description of the problem needs to be communicated as opposed to normal operation of the system so a repair person can determine that there is in fact a problem. There's a big difference between solving a problem via text as opposed to seeing what is wrong in the field. They rarely are the same.

Goodman condenser sequence of operation on a matched system. Call for cool, condenser starts, 15-30 seconds later blower motor starts, cool satisfied, condenser shuts down, 15-45 seconds later blower motor shuts down. House heats ups and a call for cool via the thermostat starts another cycle.

Based on normal operation it is impossible to determine whats wrong with the information given. There are perhaps 5 voltage measurements in the system that you could be referring to.

Aug 19, 2009 | Goodman Heating & Cooling

1 Answer

This is my first central heating and cooling unit the heat will come on and heat the house but the big fan inside the unit is not running like it did when we would run the ac is this normal


I assume you are reffering to the compressor outside not running. If so this is for A/C only. In fact once the cold is here to stay you should shut off the compressor "breaker" (located either outide next to unit or in fuse panel) and get a good quality cover for winter. This will keep the leaves and snow out of the unit. Just dont forget to take it off in the summer before you run the A/C or you will damage the system.

Sep 16, 2008 | Goodman Heating & Cooling

1 Answer

Blower starts ans stops


May be a short in the wiring or a bad control board.

Jul 07, 2008 | Goodman CLQ36AR49 Air Conditioner

3 Answers

Blower fan keeps shutting on/off,


Your blower fan turning on and off shows your thermostat is working. I am willing to bet you have the fan in the automatic condition. Check for a sticking contactor at the outside unit.

May 31, 2008 | Heating & Cooling

Not finding what you are looking for?
Heating & Cooling Logo

Related Topics:

138 people viewed this question

Ask a Question

Usually answered in minutes!

Top Heating & Cooling Experts

paulcarew

Level 3 Expert

2519 Answers

Dan Webster
Dan Webster

Level 3 Expert

8220 Answers

Donni Steen

Level 3 Expert

659 Answers

Are you a Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...