Questions & Answers for: replace heater coil Freezers

...heater coil is OK, I'd just replace the timer. It is tough to test. Finally, there is a defrost termination sensor mounted on the top of the defrost heater that shuts off the defrost heater when it ...

Ad

...heater should now come on. If it does, replace the timer. If it doesn't, check the heater and defrost thermostat. Turn the timer again till everything starts back up to end the defrost cycle. Your ...

Ad

...replace the timer. Finally, there is a sensor mounted on the top of the defrost heater that shuts off the defrost heater when it reaches a high temperature. If the coil tests OK, and you are going to ...

Question about Frigidaire Freezers

1 Answer

...If you have an adaptive defrost control instead of a timer, replace it if the heater and thermostat test good. It is located in the fridge with the controls in some models and on the back in

...heater is mounted to the bottom, and the thermostat is located on the top of the coil. I remove the thermostat and replace it with one rated at 5 degrees higher. You won't find it at Amana. I use the ...

Question about 13.7 cu. ft. / 388 liter Upright Freezer 23424

1 Answer

...replace the heater. It is necessary to perform the test on both heater leads, one at a time. Do the same thing with the defrost thermostat. However, the thermostat can not be allowed to warm up since ...

Question about 48.5 cu. ft. / 1373 liter Commercial Freezer FH2-SSB-HD

1 Answer

...If you have an adaptive defrost control instead of a timer, replace it if the heater and thermostat test good. It is located in the fridge with the controls in some models and on the back in

Question about 48.5 cu. ft. / 1373 liter Commercial Freezer FH2-SSB-HD

1 Answer

...heater melting away the ice build up on the evaporator coil. The fridge will automatically do this every so many hours. This usually last about 20 minutes or so . Here is a link for replacing a ...

Question about 72 cu. ft. / 2039 liter Commercial Freezer T-72F

1 Answer

...coil only. Freezer is stocked every other day, and is in a conditioned space. Termination switch replaced, clock works, defrost heater works. Has been sealed on top, gaskets good. Assume excessive ...

Question about 19.6 cu. ft. / 555 liter Upright Freezer EV205FXKQ

1 Answer

...replace the whole heater if one of those fuses blows. Check these fuses with a volt meter if the defrost heater doesn't work. A quick check if you have a cooling problem is to inspect the ...