No power Wow, problem solver... 10hp 5000w coleman,used 4times, 3gal of gas, monkeyed around to power up my furnace,forgot to turn off hydro from the pole , what did i fu-k up.. Hector thanks
- If you need clarification, ask it in the comment box above.
- Better answers use proper spelling and grammar.
- Provide details, support with references or personal experience.
Tell us some more! Your answer needs to include more details to help people.You can't post answers that contain an email address.Please enter a valid email address.The email address entered is already associated to an account.Login to postPlease use English characters only.
Tip: The max point reward for answering a question is 15.
Check that engine speed is where it needs to be (does it sound like it is turning too slow or too fast?).
Pull the end cover off alternator, you should be able to see the diodes for the field winding. Check the diode with a multimeter. I bet that you will find that it is defective. Also check continuity of the field winding, both wire to wire, as well as each wire to the core of the rotor. Take a look at the brushes as well for severe wear.
Oh, if the diode is blown, plan on replacing the capacitor as well.
×