Goodman CKL60AR60 Air Conditioner "start run capacitor wiring rotation" Questions

Ad

run backwards. I removed the hard start cap, removed the defective dual cap and replaced the dual cap with a known good one and everything worked correctly. you can change the rotation of the motor if

Ad

Question about Ruud Heating & Cooling

1 Answer

...the fan like that. If anyone worked on the unit before it started running like that you should make sure the capacitor is connected to the start wire and not the run wire. Let me know what you

Ad

...start capacitor is not working. You say the capacitor is ok. Are you sure the 'start' capacitor is ok, this is a tube about 6 inches long and 2 inches in diameter that triggers the start of rotation, ...

...start and run capacitors are in one can. so changing one will change the other. However look for a wiring diagram. Do not asume that both capacitors are wired in properly. They may be fighting one ...

Question about Goodman Heating & Cooling

4 Answers

...start capacitor.  This has two Black wires that are wired to the Compressor position of the capacitor and the Common position of the capacitorWiring order does not matter.  ...

Question about Goodman Heating & Cooling

1 Answer

Goodman CKL60-1 Condenser Fan Runs OK, then stops My AC is working fine, almost. The AC Unit starts up, all is well but after about an hour or so the Outside condensor fan stops running. It is still ...

...wiring and especialy the capacitor. If the capacitor has leaked fluid, replace it. If it all looks normal, take the capacitor to get it tested. You can replace the split capacitor with two capacitors ...

...start, and run, the start winding usually has more resistance. If the motor has the ability to operate at more than one voltage this can add two more windings and up to four more wires to the puzzle, ...

Question about Coleman Heating & Cooling

1 Answer

...run) and S (start) terminals. The lowest resistance will be between the C (common) and R (run) terminals. The intermediate resistance will be between the C (common) and S (start) terminals. Notice ...

Question about Heating & Cooling

1 Answer

...starts up goes through checks ok condensor fan does not run during normall operation Rotate manually, if rotates, replace capacitor and also check wiring. If can't rotate, replace bearings or

Not finding what you are looking for?
Goodman CKL60AR60 Air Conditioner Logo

153 questions posted

Ask a Question

Usually answered in minutes!

Top Goodman Heating & Cooling Experts

Paul Carew

Level 3 Expert

3808 Answers

Mike Cairns
Mike Cairns

Level 3 Expert

3054 Answers

Jay Finke
Jay Finke

Level 3 Expert

1397 Answers

Are you a Goodman Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...