MGE Galaxy 3000 UPS System - Answered Questions & Fixed issues

0helpful
3answers

I had problem with my MGE Galaxy 30KVA. The

I have a temperature fault in my galaxy 3000. Try to clean the radiator behind the cabinet with the air compresor and clean all the fan inside so air circulation is good. Don't know about batt temperature fault. Hope this help.
8/17/2022 7:26:48 PM • MGE Galaxy 3000... • Answered on Aug 17, 2022 • 660 views
0helpful
2answers

Cannot change ups mge galaxy 300 licence deadline

you can send me the executable file at [email protected] AND IWILL SEE IF THERE anything to do
2/3/2016 2:22:58 AM • MGE Galaxy 3000... • Answered on Feb 03, 2016 • 1,012 views
0helpful
1answer

Rectifier internal fault

check scr,check diodes,check driver cards
9/3/2018 6:43:55 PM • MGE Galaxy 3000... • Answered on Sep 03, 2018 • 702 views
0helpful
1answer

AC N fuse blown

The AC rectifier section circuit inside it has short circuited component/s. Contact any service technician. This is not a user repairable work. http://electronicshelponline.blogspot.com/
8/26/2015 1:53:03 PM • MGE Galaxy 3000... • Answered on Aug 26, 2015 • 547 views
0helpful
3answers

MGE Galaxy 3000 UPS, do i require to reconfigure

No you don't have to reconfigure the UPS after battery replacement. However you may have to reset the battery Timer. There are 4 possible ways.1. Press and hold the fault reset button for 3-5 seconds2. Press and hold the fault reset and security key simultaneously for 3-5 seconds3. Press an dhold the fault and alarm silence buttons simultaneously for 3-5 seconds4. Cycle the logic Power. This means to remove power from the main processor.5. Call MGE. They have the software to reset the battery replacement alarm
6/27/2018 4:24:22 AM • MGE Galaxy 3000... • Answered on Jun 27, 2018 • 1,885 views
0helpful
1answer

Tharmal overload

MAY BE YOU HAVE MISS CONNECTED THE TEMPERATURE SENSOR.
2/4/2015 12:36:16 PM • MGE Galaxy 3000... • Answered on Feb 04, 2015 • 213 views
0helpful
1answer

GE LP33 30KVA output power fails when main goes out

if INVERTER IS ON, WHEN MAINS GO OFF IF UPS FAILS AT THE SAME MOMENT YOU NEED TO REPLACE ALL BATTERY SET
2/4/2015 12:34:06 PM • MGE Galaxy 3000... • Answered on Feb 04, 2015 • 189 views
0helpful
1answer

What batteries go in this unit how many 12? need a replacement

8.3 Battery Configurations

There are different configurations for different battery types and backup time. Here, the batteries from VISION and

YUASA are selected. The backup times ranges from 1hours to 4hours for 20KVA UPS and from 1hours to 2hours

for 30KVA UPS, because of limitation of CLA power rating.

UPS Backup

time Number of blocks Type of blocks Capacity(10H)

1h 1×24 6FM55SGX 52Ah

10kVA 2h 2×24 6FM45X 2×42Ah

4h 2×25 6FM75X 2×74.5Ah

1h 24 6FM75X 74.5Ah

15kVA 2h 3×24 6FM45X 3×42Ah

4h 3×25 6FM75X 3×74.5Ah

1h 1×25 6FM90X 90Ah

20kVA 2h 3×25 6FM55X 3×52Ah

4h 2×26 6FM150X 2×144h

1h 2×25 6FM75X 2×74.5Ah

30kVA

2h 3×24 6FM100X 3×96Ah

Sheet. 4 the battery configuration with VISION battery

UPS Backup time Number of

blocks Type of blocks Capacity

(10H)

1h 2X24 NPL24-12 2X24AH

10kVA 2h 2×26 NPL38-12 2×35.3AH

4h 2×26 NPL65-12 2×60.5Ah

1h 1×27 NPL65-12 60.5Ah

15kVA 2h 2×24 NPL65-12 2×60.5Ah

4h 3×26 NPL65-12 3×60.5Ah

1h 1×27 NPL100-12 92Ah

20kVA 2h 2×24 NPL100-12 2×92Ah

4h 4×26 NPL65-12 4×60.5h

1h 3X24 NPL65-12 3×60.5Ah 30kVA

2/4/2015 12:26:02 PM • MGE Galaxy 3000... • Answered on Feb 04, 2015 • 262 views
0helpful
1answer

How to troubleshoot galaxy 3000 mge ups system 30 kv

you need the soft tuner software for G3000
2/4/2015 12:09:52 PM • MGE Galaxy 3000... • Answered on Feb 04, 2015 • 375 views
0helpful
1answer

I have an error 2-4-6

code 2-4-6 does not exist. Code 4-2-6: Personalization code is not the some on the 3 boards.

Problem locating: That's an internal failure, control GDEx, MIZx, CHAx.

Problem locating: That's an internal failure, control GDEx, MIZx, CHAx.

2/2/2015 12:32:00 PM • MGE Galaxy 3000... • Answered on Feb 02, 2015 • 182 views
0helpful
1answer

Hello, our MGE GALAXY 3000 20kva, front panel

you need an MGE expert engineer to check on the internal components, maybe the display by itself it dead can be replaced while UPS is on no problem. if you want to switch off the UPS you go for force shutdown but I cannot guarantee will restart if you do not fix the fault.
2/2/2015 11:19:53 AM • MGE Galaxy 3000... • Answered on Feb 02, 2015 • 289 views
0helpful
1answer

The lotr/litr board is faulty

replace it with the same part number.
2/2/2015 11:15:38 AM • MGE Galaxy 3000... • Answered on Feb 02, 2015 • 116 views
0helpful
1answer

What is the price of 100AH capacity batteries?

You do not need a battery, you need many. You need knowledge to replace these batteries in a safe manner. Then you do not know where to buy batteries should ask a company for help ...
1/23/2015 8:34:23 AM • MGE Galaxy 3000... • Answered on Jan 23, 2015 • 90 views
0helpful
1answer

What coolant liquid use the MGE Galaxy 3000 UPS System 10 kva

What????? No coolant liquid is ever used in any type of UPS. EVER
10/7/2014 6:16:05 PM • MGE Galaxy 3000... • Answered on Oct 07, 2014 • 635 views
0helpful
1answer

Giffgaff

Whay type of phone do you have
8/14/2014 3:02:27 PM • MGE Galaxy 3000... • Answered on Aug 14, 2014 • 46 views
0helpful
1answer

Power ware 5125 ups not charging battery

There is no Galaxy 3000
3/29/2014 12:20:19 AM • MGE Galaxy 3000... • Answered on Mar 29, 2014 • 104 views
0helpful
1answer

Self test error

Is the UPS in Bypass? Is the Inverter running? What alarms other than that code are on? Have you shut the unit down. Its best to call MGE, that unit requires to have software to work on it. Even though you find the problem, and replace the board, the Board needs to be program to that unit. YUP! This way MGE always makes money on the UPS's no matter where and no matter how old the UPS is. They lock you out. Which is unfair for the customer. The customer has no choice but to call the dealer to fix it. Trust me.. Then again when a customer buys a product, isn't it his for life? Why can't he fix his ups or hire whoever he wants besides the Manufacture? Wrong, NOT WITH MGE Products. I guess it's Job Security for MGE. That one positive thing.
3/9/2022 9:29:50 PM • MGE Galaxy 3000... • Answered on Mar 09, 2022 • 283 views
0helpful
1answer

I can get into my gmail

you must go to the MENU, and see if your configuration is o.k 2) if the internet is o.k 3) see if yout bluetooth is connected 4) if everything fail go to the support from your phone,via online chat and get the support God bless you
11/25/2013 10:55:17 AM • MGE Galaxy 3000... • Answered on Nov 25, 2013 • 36 views
0helpful
2answers

Hi How many batteries installed in mge galaxy 3000

Configurations vary, do you have a model number you can provide?If you need any UPS help contact Daniel @ Power & Systems Innovations 800.260.2259 or go to our website www.psihq.com
3/10/2015 6:18:24 AM • MGE Galaxy 3000... • Answered on Mar 10, 2015 • 585 views
0helpful
1answer

Refusing to charge

Hi Emmanel,How old is this unit? If the batteries are around 5 years old then you might need to replace them and that's why the UPS will not charge your batteries.If the batteries are new then you have an invertor issue. You will need a to have a technician come out and evaluate your needs.Reply or call me if you need more help with this -- 407.380.9200
11/1/2013 7:39:55 PM • MGE Galaxy 3000... • Answered on Nov 01, 2013 • 71 views
Not finding what you are looking for?
Computers & Internet Logo

79 questions posted

Ask a Question

Usually answered in minutes!

Top MGE Computers & Internet Experts

Grand Canyon Tech
Grand Canyon Tech

Level 3 Expert

3867 Answers

Brad Brown

Level 3 Expert

19187 Answers

Cindy Wells

Level 3 Expert

6688 Answers

Are you a MGE Computer and Internet Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...