How do you calibrate a new internal scale in a
From the main menu go to change default option,press 5454 then press enter key.after access to default nenu you have to select calibrate scal option.press again enter key then follow the on scree message.NOTE:FOR SCAL CALIBRATION YOU SHOULD HAVE 9KG/20LB OF WEIGHT.once you done so,press stop key to complete the prcess.
Model 34288. Why does it fail recharge?
=============
Make Model (what it is)
Describe Problem in the title
Mention the problem, plus everything you have done and what you are trying to do.
==============
That image is two dusty things with wires on a 'Robinair Measuring Tools and Sensors' category.
5/9/2021 12:07:29 AM •
Robinair...
•
Answered
on May 09, 2021
I have a robinair 34788 and when i tunr it on it
This is a common problem of Model: 34788,
34788-I, 34988, AC34788, GE48800 etc.
You need to replace air purge solenoid (Air purge solenoid located on
top of the ISV tank, if you open front panel cover then you can see it on top
of the tank).
After doing above stapes and your
problem still exist then you have to replace PCB relay board.
Hope
this will solve your problem, if so please vote for it for farther help! Good luck
On pulling a vacuum the
Check oil drain solenoid for any debris or damage inside the solenoid flunger. Replace/rebuild as needed. Hope this will solve your problem. Don't forget to vote for my solution