Powerware Recent Questions, Troubleshooting Help & Support

Do you work here? Claim your company

  • 160 Products
  • 383 Answers
  • 73K Views

710-12102-0X - PCBAS 9120 5-6KVA CNTL-1112NN - £107.67 + delivery + VAT from the Manufacturer - Eaton Power Quality Ltd

Powerware 9120... | Answered on Sep 15, 2013


Normally DC BUS FAULT is fixed by replacing C14 and C10. C14 is the 100uf/63V and C10 is 2200uf/16V. They are located between the heat dissipator and the logic board near transformer TX1.

Powerware 9120... | Answered on Sep 05, 2013


check the fuses inside the ups.
did the message come right after u instal de batteries or some time after?
if it came some time after the ups could have the charger damaged.
if gave the massage right after u could need to replace the fuse or u have a porwerboard problem
good luck

Powerware... | Answered on Aug 13, 2013


did u check the fuse inside the ups?
did the ups gave the error right after u replace the batteries? or some time after.
sometimes gives the message some time after and its because the charger isn´t working properly. the charger is a spare board in the 9120, 5 and 6 KVa.
good luck

Powerware 9120... | Answered on Jul 17, 2013