I have a zoneline ptac unit. The water keeps

I have a zoneline ptac unit. The water keeps overflowing and pouring out on the floor inside. We have cleaned it out and 2 days later it leaks again. Is there an internal drain line that might be plugged and where is it?

1 Answer

Anonymous

Level 1:

An expert who has achieved level 1.

Hot-Shot:

An expert who has answered 20 questions.

Corporal:

An expert that has over 10 points.

Mayor:

An expert whose answer got voted for 2 times.

  • Contributor 34 Answers
  • Posted on Aug 18, 2009
Anonymous
Contributor
Level 1:

An expert who has achieved level 1.

Hot-Shot:

An expert who has answered 20 questions.

Corporal:

An expert that has over 10 points.

Mayor:

An expert whose answer got voted for 2 times.

Joined: Aug 13, 2009
Answers
34
Questions
1
Helped
9797
Points
83

They used to use a black rubber hose to run from the front to the back of the unit on the very bottom of the unit. You may also look for a styrofoam chute . Make sure the unit is sloped to the rear slightly.

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

Heating and air unit electrical manual

http://www.geappliances.com/products/introductions/zoneline/literature.htm
0helpful
1answer

Ihave 50 ge ptac units that only the middle of evap.is getting cold

short of gas. Check for leak and arrest it. Then vacum and do gas charging.
5helpful
3answers
1helpful
1answer

Water leaking from overflow tube

pour warm water and baking soda down drain and look for cracks in tube.
0helpful
1answer

Ptec allways draines water back in to room pisspoor design

This is most likely due to the installation. The unit should have at least 1/4 inch slope towards the outside to provide for proper drainage. If it is sloped towards the inside, that's where the water will go. To check, take the unit out of the sleeve and place a level on the inside bottom of the sleeve, and check the slope. If its flat or sloping towards the inside, the sleeve will need to be removed and re-installed.

PTAC Dude
GE Zoneline Specialist
3helpful
1answer

GE Zoneline PTAC Leaking

Hi Julie,
Is this a newly installed unit? The problem sounds like the sleeve is improperly installed. The sleeve should slope approximately 1/4 inch downward from inside to outside. This way the water will run to the back of the pan where it will be picked up by the slinger fan, or drain to the outside. Most likely this is the cause, not the styrofoam pan. If you need further info, you can contact me at greg.mcnary(at)airdistributors.com (replace (at) with @) and I can get you detailed installation instructions.

Greg McNary
Air Distributors Company, Inc.
Distributors of GE Zoneline PTAC Units and
McQuay PTAC Units

0helpful
1answer

How to best run this thing

Hi Laurelrobin,
When the unit is on "low fan", it is fan only, and is recirculating room air. If the damper is open, it can also bring in outside air. If the space is not occupied for extended periods, it's OK to turn the unit "OFF", as long as you have a newer unit with Heat Sentinel, and the Heat Sentinel is turned on. Heat Sentinel will not let the room temp get above 85F, as long as the unit is OFF. Also, in most cases it's best to keep the damper closed. You can check your owner's manual for more info on the Heat Sentinel and other auxiliary functions. I also have an article on the temperature limiting functions of the GE Zoneline.

Feel free to contact me at greg.mcnary(at)airdistributors.com if you need further info.

Greg McNary
Air Distributors Company, Inc.
Louisville, KY
Distributors for GE Zoneline PTAC Units, Zoneiare PTAC Units, and McQuay PTAC Units.
0helpful
2answers

Zoneline ptac

scrap the unit for alumimun and copper and buy a forty lol
1helpful
1answer

Zoneline PTAC short circuit

Most likely you will need to either replace transformer or there may be a low voltage flat type "car fuse" usually 3 amp or 5 amp for just such an occasion. Good luck!
Not finding what you are looking for?

452 views

Ask a Question

Usually answered in minutes!

Top General Electric Heating & Cooling Experts

Paul Carew

Level 3 Expert

3808 Answers

john h

Level 3 Expert

29494 Answers

Brad Brown

Level 3 Expert

19187 Answers

Are you a General Electric Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...