Anonymous Posted on Aug 10, 2014

I have an American Standard heat pump. Replaces the capasitor last year. The blower motor will not continue to run

1 Answer

william simpson

Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

Genius:

An expert who has answered 1,000 questions.

  • American Sta... Master 1,363 Answers
  • Posted on Sep 08, 2015
william simpson
American Sta... Master
Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

Genius:

An expert who has answered 1,000 questions.

Joined: Jan 17, 2012
Answers
1363
Questions
14
Helped
318028
Points
1636

Replace it again they fail easily

4 Related Answers

Anonymous

  • 117 Answers
  • Posted on Feb 08, 2010

SOURCE: im looking for a parts list and manual for an

Instead of looking for an OEM motor which can cost an insane amount of money...

try taking the information off the motor itself and taking it to a part supply house or motor shop. i.e. an 875RPM 1/4 HP 208 V 1 PH motor with a 1/2" shaft.

Maybe taking the motor itself to the parts house or motor shop will get you further than internet searching a blower motor part number. These systems are designed so that universal parts can be put back in place....at least most of them.

Ad
hvac1960

R Subramaniyam Iyer

  • 2133 Answers
  • Posted on Dec 20, 2010

SOURCE: We need to find an

Please try with:

SERVICEMANUALS @ COST www.mauritron.com Manuals at free download:
homeappliance.manualsonline.com/manuals/.../lg_air_conditioner_product_list.html
Helpful?

Robert

  • 1036 Answers
  • Posted on Jun 20, 2011

SOURCE: the blower motor does not

Hello, turn off power to the furnace and remove the thermostat, then take the R and W Wires and put a jumper wire between them, then turn power back on if this turms on the furnace then you have a bad thermostat if it does not it is a problem with the integrated control board or possibly a low voltqge wire is loose.

Anonymous

  • 3 Answers
  • Posted on Jul 19, 2013

SOURCE: UNIT: American

What or why is there a red blinking light on front of the unit

Ad

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

American standard communicating air handler and heat pump blower wont come on new board 4 months ago any way to check the variable speed blower motor

High and low voltage AT the motor with no motor function is a bad motor. Should have 12 to 13 volts DC on r+ and r- (I believe are the correct terminals) You must test this when the machine is trying to run. Yes, it's dangerous, hire a licensed contractor!!
1helpful
1answer

Heat works until thermostat calls for aux heat, then blower shuts off with outside unit still running.

Some blowers shut off depending on the system. Do you have electric hest strips inside? If not the blower will shut off. The outdoor fan should not be running if in defrost mode. If you have heat strips then you likely have low voltage wiring crossed

If you need further help, reach me via phone at https://www.6ya.com/expert/thomas_092728000e6acb79

0helpful
3answers

American standard heat pump will only work on emergency heat with fan turned on not auto but only works a little while then quits i can turn it off for about 20 min. and back on emergency heat with fan on...

How old is the unit? Heat pumps don't work when it's real cold, you know it's limits. If it's not real cold outside, then it may be low on gas or such and need a service call.
0helpful
1answer

Amana heat pump emergency heat comes on but blower will not start. The call for heat comes in and the heating element(s) glow red for a few seconds and then there is a "click" and the heating...

Check the blower motor capicator. It should be mounted close to the motor with 2 wires to it (brown,brown/white).
Turn the blower on the thermostat and spin the squirrel cage by hand and see if it runs after by itself. If it does then definitely the capicator is bad .If it still doesn't run then check to see if there is voltage going to motor.
If thermostat is calling for fan and there is voltage present at the motor terminal then the motor is bad
0helpful
1answer

Gas furnance lights but fan does not come on. buzzing sound from panel near fan.fan is not jammed it spins freely.unit is seven years old.

Most furnaces equipped with an electronic control board activate the same blower speed for heating and continuous fan. If the cooling speed works, the problem is likely in the circuit board (relay) or wiring to the motor. Check and rectify.
5helpful
1answer

I have error codes flashing on my thermostat..it is an american standard model the manual for the therm. has ACOT900AC43UA on front..says to find addedum 18-HD32D2-1/69-2009 for codes i cannot find it...

Error codes from American Standard Pub 18-HD32D2-8, which is a one-sheet document that came with my American Standard air-conditioner:

29 = not listed

129 = not listed

80 = HPCO Fault - problem is in outdoor unit - Desscription: High Pressure Monitor Fault (hard lock out, cycle power to reset)

91 = Communication Inactive Fault - problem is in air handler - Descriptions - COMM Bit Master Clock Error, COMM Heat/Cool Demand Error, Serial Motor Communication Inactive Error

91 = Communication Fault - problem is in furnace - Descriptions: Blower motor no COMM response, Inducer motor no COMM response, Loss of heat/cool demand, Loss of clock signal

91 = Communication Fault - problem is in outdoor unit - Descriptions: Loss of Heat/Cool Demand Message (COMM), Loss of Bit Master (Clock Signal)

91 = Communication Fault - Description: Comm line is dead and no bits have been received.

By the way, I do not recommend American Standard. I've had mine 14 months and it just blew up - the entire control panel blew. My advice to you - think about a different brand.

Nancy
Scottsdale, Arizona
1helpful
2answers

American Standard blower will not run

Sounds like motor has failed. If the red light is blinking it may be telling you what is wrong by the number of blinks. It maybe locked out for some reason or loose wire. Try turning off breakers to inside unit for 5 mins and try again, this may reset unit. But it sounds like a bad motor or circut board. Try running with stat in on position instead of auto in cooling mode.
Not finding what you are looking for?

97 views

Ask a Question

Usually answered in minutes!

Top American Standard Heating & Cooling Experts

Steve Sweetleaf
Steve Sweetleaf

Level 3 Expert

1212 Answers

Paul Carew

Level 3 Expert

3808 Answers

Brad Brown

Level 3 Expert

19187 Answers

Are you an American Standard Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...