SOURCE: Ruud Achiever 90 Plus wont start
4 blinks is "pressure switch closed" there are 2 in the system according to the wiring diagram one for the vent system and one for the drain system ... I just wiggled them and heard one "click" the fault light quit blinking and when I pushed the safety switch back in the furnace fired right up. That being said is there a good website for learning how to maintain your own furnace? I'll call a pro if I have to, but shoot I can fix a jet engine... this shouldn't be much worse.
Thanks
dan
SOURCE: ruud achiever 90 plus blower not working
does the furnace ignite?? your system may not have been lighting and has gone into ignition lockout count the codes of the led lights then remove panel led diagnostic codes are listed there.
if led codes indicate no problem verify capacitor is good and that mtr is getting 115 volts.
SOURCE: RUUD Furnace not coming on
the fuse that your refering to is on the control board indie of the furnace. shjould be a 3 amp. good luck.
SOURCE: Ruud achiever 90 plus won`t start at times
sounds like you have a heat pump heat pumps dont work below 30* temps you should have some type of backup heat
SOURCE: My Ruud Achiever 90 Plus not blowing cooled air
Look on the condensor, (outdoor unit) at the very bottom of the rear panel and you should find a red reset button. push it. If that does not solve the problem, and the outdoor unit is running (make sure both the fan AND the compressor are running) then you are looking at a low refridgerant issue and possibly dirty coils.
In that case, clean the coils and have refridgerant added.