Question about Paragon 8145-20 Defrost Timer
SOURCE: On a Paragon 8145-20 Defrost
Link below has 8145-20 wiring diagram:
http://waterheatertimer.org/Paragon-timers-and-manuals.html#defrost
Terminal N is 2nd wire needed to complete circuit.
In 240V 8145-20, there are two hot wires.
One Hot connects to terminal 1, with jumper to terminal 2.
Second Hot connects to terminal N, and this will power the clock motor and timer.
Terminal X is for temperature or pressure termination switch.
Defrost cycle works like this:
Timer is running but switched OFF.
Refrigeration fan is ON.
Timer switches ON, defrost cycle begins.
Refrigeration fan turns OFF.
Hot gas defrost turns ON.
When temperature-or-pressure limit switch reaches trip point, it switches timer OFF.
Refrigeration fan turns ON again.
Hot gas defrost turns OFF.
Posted on Jan 20, 2011
SOURCE: What purpose does the solenoid
The solenoid switches timer OFF when temperature-or-pressure limit switch reaches trip point.
http://waterheatertimer.org/Paragon-timers-and-manuals.html#defrost
Posted on Jan 20, 2011