Hi i have Fujitronic FA-1300 Dual Hose 13000 BTU Portable Air Conditioner the air comes out it not cold does it need gas?

1 Answer

Anonymous

Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

Brigadier General:

An expert that has over 10,000 points.

  • Master 4,736 Answers
  • Posted on Aug 24, 2011
Anonymous
Master
Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that got 10 achievements.

MVP:

An expert that got 5 achievements.

Brigadier General:

An expert that has over 10,000 points.

Joined: Jan 15, 2011
Answers
4736
Questions
0
Helped
2105162
Points
14643

Before assuming it needs to be recharged with refrigerant gas, check the following. As all of these things can affect the cooling,

1. Remove and clean the air intake filter.

2. Check exhaust hoses for obstructions.

3, Exhaust hoses may have to much downward droop. Which doesn't allow the air to exhaust as it
should.

4. check for holes or leaks in the exhaust hoses. Repair or replace the hoses as needed.

5. Check the temperature setting on the controls, as it may be set to high.

If none of the above solves the problem, it may need to be recharged with refrigerant gas. hich is best left to the pros.

I hope this helped you and thanks for choosing FixYa.

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

Hi, how to you add more freon to 9,000 btu fugitronic portable a/c? Thanks

From the condensing unit you can see two valves. Connect the blue hose to the bigger pipe sometimes marked "S" to the suction manifold gauge with the blue dial.The discharge valve "D" is the smaller pipe and connect it to the red hose going to the red dial gauge. After connecting the hoses respectively, open the blue handle of the manifold to release air from the blue hose and close it. The same thing should be done to the red handle valve of the manifold. Connect the yellow hose to your freon cylinder and slightly open the cylinder valve while connecting it to the middle of the gauge manifold. Now, there is no air from all hoses and you can start charging freon when the unit start running. Check suction pressure and the Rated Load Ampere of the unit
0helpful
1answer
1helpful
1answer

FA 1300 NOT COOLING WELL. IT SEEMS TO KICK ON BUT THEN TURNS OFF AND IS NOT BLOWING COLD AIR

Hi there. If unit just starts to get cold then the compressor shuts off and if the compressor comes back on after 3 to 5 minutes, the system has a freon leak or the compressor is over heating.
If you are technically inclined, search for leaks using soapy water at all tubing connections.
For overheating compressor: Clean the condenser with compressed air or vacuum cleaner. If still overheating, start switch or start capacitor may be bad.
Thanks
Paul
0helpful
1answer
0helpful
1answer

Fujitronic 1300 ~ compressor does not stay on and not overly cold

sounds like the units compressor is shutting off. this could be caused by being low on freon, or a dirty condensor coil. the condensor coil is where the hor air exits the unit. make sure it is clean, free of lint/dirt. if it is clean, you will need to take it in to a repair shop and have the coolant leak found/repaired and then recharge the unit.
1helpful
1answer

Exhaust hose replacement parts for Fujitronic Model FA-1300

hello! there,try to website particular service parts mostly on your location where you live,try on google.com and try to type your brand and model then press enter they will give several service center to select that is more conveinient to your place and quality service.and exact price unit feel free to ask any want to purchase.have a good day.and thanks
0helpful
1answer

Our Fujitronic FA-900 Portable AC is not running cold like it used to.

Try A.B. May they are out of Kansas City but they will travel up to 90 miles I have heard.
Not finding what you are looking for?

181 views

Ask a Question

Usually answered in minutes!

Top Heating & Cooling Experts

Paul Carew

Level 3 Expert

3808 Answers

john h

Level 3 Expert

29494 Answers

Brad Brown

Level 3 Expert

19187 Answers

Are you a Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...