LG LP1200DXR Portable Air Conditioner - Answered Questions & Fixed issues


You have to try resetting the system. First turn the breaker off for the condenser and wait about 20 seconds. After you turn it back on the system should reset Air Conditioning Tamarac

LG LP1200DXR... | Answered on Aug 15, 2016 | 639 views


Indoor Pipe Sensor or Outdoor Sensor Assy fault, Open or Short. Disconnect from PCB and measure resistance. Air sensor = 10 kOhm at 25C, Pipe sensor = 5 kOhm at 25C. If not replace sensor.

LG LP1200DXR... | Answered on Feb 09, 2016 | 273 views


there should be an upper drain and lower drain in the back bottom of the unit unplug the drain plug and voila!!

LG LP1200DXR... | Answered on Sep 09, 2015 | 193 views


Depends on where you live and how much you care about your cat. I wouldn't.

LG LP1200DXR... | Answered on Jun 11, 2015 | 75 views


tip the zircon back a little bit and water will pour our. I did this because i had the same problem. This solves it

LG LP1200DXR... | Answered on Dec 23, 2014 | 3,623 views


If it hasnt been drained then there is likely a float switch that is keeping the compressor from running so that it doesnt overflow.

LG LP1200DXR... | Answered on Aug 19, 2014 | 196 views


Wrong site for that

Just a chat room

LG LP1200DXR... | Answered on Aug 22, 2014 | 429 views


portable air conditioner need clean condenser .

LG LP1200DXR... | Answered on Jul 16, 2014 | 134 views


Check your fuel filter & purge the pump

LG LP1200DXR... | Answered on Dec 16, 2013 | 76 views


All air conditioners collect condensate. It has to drain somewhere. Try connecting tubing to the drain hole or port. In order for air conditioners to remove heat from a space, they also remove humidity, which is water vapor in the air. Like placing a cold beverage in a warm room, it will form condensate (water) around it. The water that you were trying to drain out already leaked out. This is a normal thing for condensation to form when cooling. The condensate needs to be emptied regularly or piped with flexible tubing to a window or plumbing.This is the same as water dripping from your car while the A/C is on.

LG LP1200DXR... | Answered on Jun 10, 2015 | 286 views


After reading over the Owner's Manual for your unit, I wonder if you are operating it in the Cool & Dry Mode. If that's the case, the dehumidifier is in operation, which would account for having to drain the unit every 2 to 3 hours. Ideally, the Cool and Dry Mode should only be operated for about an hour, when the unit is first started . Removing the humidity will allow the AC function to cool more effectively. But, it is not necessary for it to remain in Cool & Dry mode all the time. Because the AC itself unit will remove some humidity too.

Hope this helped you to troubleshoot and solve the issue of having to drain the unit every 2 to 3 hours

LG LP1200DXR... | Answered on May 31, 2013 | 1,353 views


It still has a leak, just a small one. This needs to be found and fixed. Check all flexible connections first, look for signs of oil, it comes out with the refrigerant.

LG LP1200DXR... | Answered on Sep 07, 2012 | 66 views


No es necesario a?adir agua al tanque de aire acondicionado port?til. Cuando la unidad funciona, se genera es el agua de la condesation en la habitaci?n. La adici?n de agua, significa que usted tendr? que darin el tanque con m?s frecuencia.

Espero que esto
te ayud? y gracias por elegir FixYa.

LG LP1200DXR... | Answered on Sep 22, 2011 | 275 views


Actually, your unit was not designed for continuous draining. It needs water in the tank to help cool the coils. I'm sort of surprised that the unit hasn't stopped cooling or hasn't overheated. Since you haven't seen any water in the drain tank you have, it may have pasted the point of no return. Disconnect the hose, reinstall the drain plug and hope that you have to start emptying the tank again, soon.

Hope this helped you and thanks for choosing FixYa.

LG LP1200DXR... | Answered on Aug 20, 2011 | 1,135 views


In AC mode, the unit still has some dehumidifying properties. So, it may be that there is more humidity in the air this Summer, than in prior years. Having to empty the tank every 24 hours is not unusual. Be sure that the air intake filter is clean & check the exhaust hose for obstructions.

Hope this helped you & thanks fr choosing FixYa.

LG LP1200DXR... | Answered on Aug 13, 2011 | 778 views


clean the unit,

LG LP1200DXR... | Answered on Jul 31, 2011 | 324 views


Check the fan capacitor.bobicehouse_36.jpg

LG LP1200DXR... | Answered on Jul 22, 2011 | 67 views


Hi,
Either the unit is low on freon or the freeze sensor is bad...sensor or control board that is....
Anyway the coil is either getting too cold or the unit thinks the coil is too cold and is shutting down...

You will have to troubleshoot the exact problem or have someone check it for you...

heatman101

LG LP1200DXR... | Answered on Jul 17, 2011 | 967 views

Not finding what you are looking for?
LG LP1200DXR Portable Air Conditioner Logo

85 questions posted

Ask a Question

Usually answered in minutes!

Top LG Heating & Cooling Experts

Marvin
Marvin

Level 3 Expert

85239 Answers

Steve Oakes
Steve Oakes

Level 2 Expert

234 Answers

Muntejaya Ginting
Muntejaya Ginting

Level 3 Expert

10422 Answers

Are you a LG Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...