Carrier 38BRC036 Air Conditioner Questions & Answers
Carrier Celesta R - error
E-4 ..........short of asor no gas/E4 is an "Abnormality of Outdoor Unit."Find leak and arrest it. Recharge gas.
I have a carrier furnace
code 33 LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - If open longer than threeminutes, code changes to #13. Flame roll-out switch requires manual reset.Check for: - Dirty filter or restricted duct system. - Loose blower wheel.- Defective blower motor or capacitor. - Defective switch or connections.- Inadequate combustion air supply (Flame Roll-out Switch or fuse link open).- Open Flame Roll-out switch, or fuse link. Manual reset or replace.
Motor blade not moving, motor
sounds like the fan motor is at fault , 1 it could have bearing problems 2 the capacitors if it has are at fault , to correct check fan with out power to see if it runs free if it runs smooth then i suspect the capacitors are at fault , you will need a megger to check both items , make sure you check that they both accept a charge of 500 volts and that they discharge , if one does not , then change for a knew one ,