20 Most Recent Rheem RQPMA037JK R410A All-in-One Package Unit Heat Pump Questions & Answers


42 would be a 3.5 ton

I’m happy to help further over the phone at https://www.6ya.com/expert/vincent_f7b7c5f4dedd2565

Rheem RQPMA037JK... | Answered on Mar 03, 2015


that reset is for the high pressure switch. this means your compressor is getting to hot which is then increasing the pressure and tripping the switch because the fan isn't running. usually if a capacitor is bad you can give the motor a "kick start " and the blade will then start turning. use a long stick or screwdriver to spin the blade but then you will know you need a cap. that switch is protecting your compressor, don't hold it down to keep it running.

If you need further help, reach me via phone at https://www.6ya.com/expert/thomas_092728000e6acb79

Rheem Heating &... | Answered on Oct 14, 2017


Likely a bad motor. If you have a meter and electricity confidence you need to verify that you have high and low voltage AT the motor. If both voltages present and still no motor you know it's bad. If no low voltage, possibly have a bad control board.

If you need further help, reach me via phone at https://www.6ya.com/expert/thomas_092728000e6acb79

Rheem Heating &... | Answered on Sep 16, 2017

Not finding what you are looking for?
Rheem RQPMA037JK R410A All-in-One Package Unit Heat Pump Logo

3 questions posted

Ask a Question

Usually answered in minutes!

Top Rheem Heating & Cooling Experts

Lawrence Oravetz

Level 3 Expert

10548 Answers

ray gallant

Level 3 Expert

70046 Answers

 Russ Hill
Russ Hill

Level 3 Expert

4057 Answers

Are you a Rheem Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

View Most Popular

Rheem Heating & Cooling

  • Rheem Heating & Cooling

Most Popular Question

btu capacity ahr42c3xh21b

  • Heating & Cooling
Loading...