1answer

Amana furnace has turns on for a minute then off, it may stay on for a few minutes or seconds and repeats...we have heat, but blower is intermitten...what do i do???

You will need to verify that you have constant high and low voltage AT THE MOTOR. If the voltage remains constant and the motor still running intermittently then the motor is bad. If you need further help, reach me via phone at https://www.6ya.com/expert/thomas_092728000e6acb79
12/6/2017 5:54:46 PM • Amana Heating &... • Answered on Dec 06, 2017
0helpful
1answer

There is a burning smell when the heat is turned on my Amana PTC093B35AJ wall unit. How do I eliminate it?

just let it run, it should go away after a few cycles. dust accumulates in the elements, just needs to burn off. if smell persist after 12 hours may want to have it looked at. If you need further help, reach me via phone at https://www.6ya.com/expert/thomas_092728000e6acb79
11/11/2017 5:01:33 PM • Amana Heating &... • Answered on Nov 11, 2017
0helpful
1answer

Have amana furnace model GACA070AX30. FURNACE HAS A 5 FLASHES ON ERROR CODE. FURNACE STARTS UP REACHES THERMOSTAT SETTING, BURNERS SHUT OFF BUT FAN MOTOR WILL NOT SHUT OFF. IT ALSO TRIPS ROLLOUT LIMIT

This is a dangerous situation. If your rollout is being tripped open, the heat is going where it should not be going. The fan stays on because it is designed to dissipate the heat.
11/3/2017 7:29:07 PM • Amana Heating &... • Answered on Nov 03, 2017
0answers
0helpful
2answers
0helpful
1answer

4 ton Amana -heat comes on sporadic in spring and fall (Every season change) Heat worked through 20 degree weather. Thermostat at 74. Today is 100% humidity and 52 degrees outside and heat won't work

Assuming this is a heat pump I'm guessing you have a bad temp sensor. Your outdoor fan is likely controlled by a temp sensor so it only runs as needed during heating. Fan not coming on and compressor still needs cooled therefore compressor protection kicking in????? If you need further help, reach me via phone at https://www.6ya.com/expert/thomas_092728000e6acb79
8/12/2017 8:40:18 PM • Amana Heating &... • Answered on Aug 12, 2017
0helpful
2answers

AC not blowing cold air

Remove the outside fuse from the unit that is not cooling... remove all the sheet metal from around the outside unit.. see if there is a lot of grass/weeds/ bird nests, or other material in the coils.. if there is... use a high pressure hose to clean the coils completely!!!!! (I had this done to mine...worked much better!!)..if this doesn't help,, I am afraid it might be time for some freon... and yes..its $$$$...
8/11/2017 12:01:05 PM • Amana Heating &... • Answered on Aug 11, 2017
0helpful
1answer

Water is draining outside my Amana 80 sse furance, how do i drain the pan

The drain is likely clogged. Take a shop vac to the drain on the exterior of the home. Hopefully this will clear the drain line. If you need further help, reach me via phone at https://www.6ya.com/expert/thomas_092728000e6acb79
8/5/2017 11:33:44 PM • Amana Heating &... • Answered on Aug 05, 2017
Not finding what you are looking for?
Amana PTH153B35AE Air Conditioner Logo

9 questions posted

Ask a Question

Usually answered in minutes!

Top Amana Heating & Cooling Experts

Mike Cairns
Mike Cairns

Level 3 Expert

3054 Answers

Jay Finke
Jay Finke

Level 3 Expert

1397 Answers

Cindy Wells

Level 3 Expert

6688 Answers

Are you an Amana Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

View Most Popular

Amana Heating & Cooling

  • Amana Heating & Cooling

Most Popular Question

amana ptac

  • Heating & Cooling
Loading...