Friedrich D50C Dehumidifier - Answered Questions & Fixed issues
Friedrich dehumidifier
Most dehumidifiers have a "Frost Guard" mounted on the condensor coil. If frost accumulates on the condensor coil the frost guard turns the compressor off until the frost melts, then comes back on again. For the dehumidifier to work properly, the surrounding (ambient), temperature must be higher than 65 degress. This temperature allows the moisture in the air to condense on the coils and drip into the reservoir without freezing up on the condensor coil. Also, if the humidity is too low, (below 45%), the same condition will occur. So it will help to keep the parameters in mind when you have this issue.
Thank you for your allowing me to advise you on this issue.
Dave E. (Illeagle)
I bought the FriedrichD50.
Yes, it does make sense, depending on what humidity extraction level you have it set on. Set to high, it will will remove little to low condensation/humidity. Set it to 35% or if you have an analog model (no LED screen) set the humidity extraction knob on Maximum Also, be sure that the air intake filter is clean.
Thanks for choosing FixYa.
Why does the fan run non stop? the compressor
Depending on the time sequence you have this unit set to run, Fredrich's are designed so that the fan runs almost constantly, to keep the air moving. When it senses a rise in humidity above the level you have it set on, the compressor turns ON and runs until the level of humidity is lowered. This is especially true, if you are operating this unit in continual mode.
Hope this helps you and thanks for choosing FixYa.
How do you set it to come on and off automatically
Generally, setting the humidity extraction level to what you want (Remember, the lower the percentage, the more humidity will be extracted) and not operating it in continual run mode will do the trick. Most humidifiers can be set to run in a 2 hour or 4 hour intervals. That means it will run as necessary for 2 or 4 hours and then turn OFF. It will turn back ON again, when the humidity level in the home rises above the setting you have it on.
Hope this helped you. Please let me know. Thanks.
D50c
Most dehumidifiers have a "Frost Guard" mounted on the condensor coil. If frost accumulates on the condensor coil the frost guard turns the compressor off until the frost melts, then comes back on again. For the dehumidifier to work properly, the surrounding (ambient), temperature must be higher than 65 degress. This temperature allows the moisture in the air to condense on the coils and drip into the reservoir without freezing up on the condensor coil. Also, if the humidity is too low, (below 45%), the same condition will occur. So it will help to keep the parameters in mind when you have this issue.
Thank you for your allowing me to advise you on this issue.
Dave E. (Illeagle)
Just bought a dehumidifier in
It isn't necessary you run it 24 hours a day. You can set it to be on for 2 or 4 hour intervals and then it Turns OFF. However, I am a bit concerned that you have the humidity extraction level set a bit high for a basement application. 50% is more than most basements need to be. Lowering it to 35%, will remove more humidity and eventually will run for shorter periods of time. It takes several days of operation for the dehumidifier to get the humidity under control.
If you have a floor drain in your basement, you can use a hose to daring the water, rather than having to empty the bucket daily (which is not that unusual). See your Owner's Manual on how to connect a 48" length of garden hose to the dehumidifier.
I hope this helped you & thanks for choosing FixYa.
9/17/2011 1:39:53 PM •
Friedrich...
•
Answered
on Sep 17, 2011
•
790 views
I have a 14 month
The problem you're having may be due to the plastic drain tubing to the water collection bucket benig clogged. To solve this problem, do the following:
Turn the unit OFF & unplug it.
Remove
the water collection bucket and look up inside the bucket holder
cavity. You will see either a drain hole or small tubing that drains the
water into the bucket. Using an appropriately sized, 18" long, plastic
Zip Tie, carefully insert the tip of Zip Tie into the hole or tubing.
Continue to push it in until you reach a bend in the tubing. You will
need to gingerly work the Zip Tie past this bend, until it either
bottoms out or you run out of usable Zip Tie. Then slowly pull the Zip
Tie back out while rotating (twisting) it. This will breakup any clogs.
As you reach the inserted end of the Zip Tie, be prepared, as some water
may follow. Reinstall the bucket properly, plug the unit in and turn the Master
ON/OFF Switch to ON. Set the humidity extraction level to 35% or
Maximum if you have a manually controlled unit. Allow the unit to run,
while you monitor it for any leakage.
NOTE: If you don't have a Zip Tie, you may use something similar ( i.e.a long pipe cleaner), but NO wire coat hangers.
Hope this helps you to solve the problem. Thanks for choosing FixYa.
9/16/2011 1:25:57 PM •
Friedrich...
•
Answered
on Sep 16, 2011
•
533 views
Brand new dehumidier 2 weeks old, is not removing
There are 5 basic, but solvable reasons for what you described. Please pay particular attention to numbers 1 & 2.
1. The humidity extraction level is set to HIGH. Lower it to 32-35%.
2. Air intake filter is dirty or clogged. Turn unit OFF, & Unplug the
Unit, before removing to inspect & clean it, if necessary. If washed,
allow filter to completely dry before reinstalling. DO NOT operate
the unit without the filter.
3. Obstructed air flow. Maintain a minimum of 12 to 18" of clear air
space around the entire unit.
4. Cooling coils are dirty and need to be cleaned. Use warm water & dish washing liquid to
clean the coils. Rinse and wipe dry. Apply a light coating of WD40 to the coils.
5. Ambient air temperature at floor level is between 40 - 60 degrees.
dehumidifiers do not work well between those temperatures
(Unless, you have a Low Temp Unit). This applies mainly to
where the air
temperature at floor level is colder than at shoulder level
in basement applications. Raising the unit up off the floor,
onto a sturdy table, counter top, etc, that can handle the weight
of the unit, plus a full tank of water, will usually resolve this
problem.
If
none of the above solves the problem, it may be a case of the
compressor needs to be recharged with refrigerant gas or that the Humid-i-stat sensor has failed. These things usually occur in units that are
5 years old or older. It's rare in a unit younger than that. But, it
can happen.
No all of the above may apply to your circumstance, but keep them in mind for non water collecting problem. Thanks for choosing FixYa.
8/24/2011 12:06:21 PM •
Friedrich...
•
Answered
on Aug 24, 2011
•
653 views