If this is a mini split ductless there is a control wire with 3-4 wires inside (normally red, white, blue and green) that is connected from the outdoor unit to the indoor unit. This wire feeds voltage from the o.d. unit to the I.d. unit. If all connections at the o.d. unit are good, then check for voltage at these connections at the o.d. unit. If no power at these connections then a circuit board has faulted. Call a tech. and have a tech support number ready (1-800#) in case your service tech don't have it.

Sanyo KHS0971... | Answered on May 19, 2015


Hi Eugene, try replacing the remote control batteries
You can do a test to see if your remote control is broadcasting
Take your cell phone, put it in camera position and point the emitting LED of the remote control towards the camera, press any of the keys and see if you notice that a light emits, if so, the remote control is fine, if not, replace the remote control
I hope you can solve the problem
Regards Franco Dosil

Hola Eugene, prueba reemplazar las pilas del control remoto
Puedes hacer una prueba para saber si tu control remoto esta emitiendo
Toma tu celular, ponlo en posicion de camara y apunta el Led emisor del control remoto hacia la camara, presiona cualquiera de las teclas y observa si notas que emite una luz, si es asi, el control remoto esta bien, si no, reemplaza el control remoto
Espero puedas resolver el problema
Saludos Franco Dosil

Sanyo Heating &... | Answered on Aug 26, 2019


https://lmgtfy.com/?q=khs0951+filter

Sanyo Heating &... | Answered on Aug 25, 2019


Could be the wrong part in the right box??? It does happen.

Sanyo Heating &... | Answered on Jul 10, 2019


Possible, Refrigerant not flowing due to shut valves or solenoid problem.
Condensation cut off sensor also possible

Sanyo Heating &... | Answered on Jul 03, 2019


If it is new split air conditioner with a four way valve and it stops giving heat. Check if there is any power going to the coil of the four-way valve. Check also the continuity of the coil. If there is power and the continuity, replace the four-way valve. If you don't get power going to the coil, check the wiring. If wiring is good, replace the electronic control board.

Sanyo Heating &... | Answered on Jan 11, 2019


The drain is plugged or the unit pump is not working. Check those two things

Sanyo Heating &... | Answered on Sep 20, 2018


indicates a blockage in the suction line , evaporator , tx valve

Sanyo Heating &... | Answered on Feb 04, 2018


check the unit drain tube, missing or not connected correctly

Sanyo Heating &... | Answered on Sep 10, 2017


Recheck the wiring. Pay special attention to the wiring splices with those triangular doo dads on them.. that is where my issue was! Wires was just eaten away by the elements.

Sanyo Heating &... | Answered on Sep 09, 2017

Not finding what you are looking for?
Sanyo KHS0971 9,000 BTU Ductless Mini-Split Wall-Mounted Heat Pump & Air Conditioner Indoor Unit Logo

1 questions posted

Ask a Question

Usually answered in minutes!

Top Sanyo Heating & Cooling Experts

Dennis Boxerman

Level 3 Expert

1305 Answers

jdthefixer

Level 3 Expert

747 Answers

Harrie

Level 3 Expert

6746 Answers

Are you a Sanyo Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

View Most Popular

Sanyo Heating & Cooling

  • Sanyo Heating & Cooling

Most Popular Question

no power interior unit power everywhere

  • Heating & Cooling
Loading...