Pentair IntelliFlo VS-3050 & VS+SVRS Variable Speed Pump - - Page 7 Questions & Answers
Code pentair code 128r14
Your main bord model number and Revision. model 128 Revision 14. This will appear every time the system reboots.
Pacfab mimimax 100 doesn't stay on
if still has power check gas pressure if ok check burner tubes for blockage if unit tripps breaker check ignitor if lights but goes out check flame sensor
What is pentair code ad0
ado is a code for stack flue temp set up if you look at a pentair chart you can find the procedure to change that
Pentair VS pump slows down. Why?
The pump is running at prime speed at start-up. Your highest speed (number on panel) might be much lower than prime.
Try setting the rpm for the speed number you select a bit higher. You will need to know how to adjust and lock in the rpm you want.
Heater shuts down after 30 sec. get e05 error code replaced the SFS have same problem .
I had same issue yesterday in the field. The sensor was bad in my case. After replacement of the Stack flu sensor my stack temp was only reading 80 degrees, a clear indication that the board needed to be replaced as well.
Replaced board and the heater fired fine and the stack temp reading was normal, 300 degrees.
To obtain a stack temp, after the heater fires hold down the pool or spa button until the temp appears in the display. It will time out after 10-15 seconds.