We have a sandwich makeline
If you are relating to the fan that is with the compressor, DO NOT RUN UNIT WITHOUT THIS FAN RUNNING. You can overheat the compressor and kill it. Some of these units use small plugs on the fan wires and it could have been pulled loose when the unit was moved. If you find the plug, be sure it is plugged in physically. Don't trust it just because it looks like it is plugged in. It may not be making a good connection.
9/29/2017 2:39:04 AM •
True...
•
Answered
on Sep 29, 2017
Cant get it down far enough...11 degree temp,low pressure is 24.5,hi pressure is 275 been running for 4 hrs straight. This is a True three door freezer,about 4 yrs old ,has 404a refrigerant
If the unit is indoors, the pressures are not that bad. I would look for possible issues with air flow. Maybe heavy frost forming on evap. If not, then go to basics. Remove charge, replace filter/dryer, pull good vacuum, weigh in the charge. This usually eliminates most problems.
7/28/2017 2:12:30 AM •