...wire for the fan. W1 or W2 terminals are usually resevered for the heat leg. Disconnect them both, put those wires out of the way, Put door back on and turn power back on nothing should be operating. ...
...W1,W2,Y,E, and an O wires.My new honeywell rth7600d doesn't have a spot for both O and W1?? Should I not connect O? The directions aren't explaining enough. This will depend on type of system, ...
...wire W2 from the indoor unit goes to W2 on t'stat. You don't need any wires from W1on the indoor unit to W1 at the t'stat because with a York heat pump Y1 is the contactor which turns the compressor ...
...W2 can just go to W and E stays disconnected. But before I do anything, I just want to make sure. Thanks for the help in advance You have a heat pump. You need a thermostat for "Heat pump with ...
Question about Dayton Heating & Cooling
wire inside the heater going from this "W2" connection. Doesn't this leave the circuit open? The notes next to the wiring diagram talk about removing "jumper W1 to W2 when 2-stage thermostat is used."
...W2/Y1/Y2/ is another example. Write down colors of wires where they went to those letters and then remove them. Make a jumper wire and put between R and W1(W). put bottom door back on and turn power ...
W2,W1,O,C. 1 wire has a red to the R,then yellow to the Y, Green to G, Blue is not connected,white is connected to both W2 and W1. The next line has only 2 lines connected white to Y and red to C. The