I Have the above air con unit 18 months old the cooling fan appears to be off all the time and an error code "LT" appears on the display after a few mins. I would like to know what the error code is before I continue to check the functionality of the fan any thoughts? thought it might be Low Temp

Posted by on

1 Answer

  • Level 2:

    An expert who has achieved level 2 by getting 100 points

    MVP:

    An expert that gotĀ 5 achievements.

    Governor:

    An expert whose answer gotĀ voted for 20 times.

    Scholar:

    An expert who has written 20 answers of more than 400 characters.

  • Expert
  • 61 Answers

I was trying to identify a error code, I found a manual online after a while

Posted on Sep 02, 2008

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

2 Answers

Error code e6 what does that mean air conditioner will not start


DeLonghi CF210 Portable Air Conditioner Error code e6 ...

www.fixya.com > ... > DeLonghi CF210 Portable Air Conditioner
DeLonghi CF210 Portable Air Conditioner, error code e6 related issues. Get free help, solutions & advice from top DeLonghi experts.

Error e6 displaying on single split model one - Fixya

www.fixya.com/.../t4492271-error_e6_displaying_single_split_model
Apr 5, 2010 - Question about DeLonghi CF210 Portable Air Conditioner ... then the code error display E6 and the error code is Communication malfunction.

DeLonghi fix e6 error Air Conditioners Questions & Answers ...

www.fixya.com > Forum > Tags > fix e6 error > Air Conditioners
DeLonghi air conditioners fix e6 error related questions and answers. ... DelonghiFX400eco error code I Have the above air con unit 18 months old the cooling ...

DeLonghi CF210 Portable Air Conditioner Error code e6 split


Jan 01, 2016 | DeLonghi Air Conditioners

1 Answer

My air-con is not as cold as before. I tried to lower the temperature, but when i try setting the temperature to 18 degrees, the remote just shows 18 degrees for like 5 seconds before going back to 31...


These is because you have not service your air-con for a long time. The cooling fins are clotted with dirt & dusts accumulated for a long period of time, and the water vapour caught between the cooling fins turn into ice when you set lower the temperture for the air-con. Moreover cool air from the blower/fan cannot pass thru', the cooling fins to regulate the cool air into your room.

You have to get the professionals to do a service on your air-con.

Hope it clarify your predicaments.

Jun 15, 2011 | Sanyo Air Conditioners

1 Answer

Hi On our portable DeLonghi air con, we have


Temp setting is very low. Raise it. And also service your unit frequently.

Dec 24, 2010 | DeLonghi PAC C100 Air Conditioner

1 Answer

Hi there i have a delonghi one split system air con. unit cools good for a minute or so then starts to struggle blowing warmer air. i have noticed the condensor fan on the unit out side does not turn on....


Either the fan motor outside is bad or the run capacitor for it is bad. One quick way to tell, you just have to be really careful, when the compressor turns on get a long screwdriver and spin start the fan. If it starts turning then simply replace the start capacitor, which more than likely will look bloated. If it doesn't start then you need to replace the motor.

Oct 06, 2010 | DeLonghi Air Conditioners

1 Answer

Not Cool


Measure room and calculate btu's

Formula Length times Width times Height Times Eighteen divde by Five.

Example: 12 x 15 x 9 x 18 / 5 = 5832 BTU's

Jun 03, 2010 | Panasonic CS-A12C Air Conditioner

1 Answer

DE500P Dehumidifier: Does not dehumidify even though set to dehumidify. Fan will turn on when RH above setting, and stay on, since humidity doesn't drop. Filter is clean & pail empty.


Locate and touch the cooils located, usually, above the condensate collection pan, ("pail empty"). If the coils are not cold, or cool to the touch, the unit has lost its charge of refrigerant. This would explain why the unit fan is working, but there is no condensate, as there is no coolant (charge) to cool the coils and "pull" the hunidityout of the air.

Jul 07, 2008 | DeLonghi Air Conditioners

1 Answer

RADEL CR 208 PORTABLE AIR CON UNIT


DOES ANYONE ACTUALLY ANSWER ANY PROBLEMS ON THIS FORUM?????????????????

Jun 24, 2008 | Air Conditioners

1 Answer

FX-160 not working


Check your voltage in your area or check your outlet it may be loose. If your outlet is loose try using another outlet to test the unit.
May be the unit is tripping due to abnormal voltage or loose outlet.

Dec 29, 2007 | DeLonghi Pinguino PAC-02 Air Conditioner

Not finding what you are looking for?
DeLonghi Pinguino PAC-GSRU Air Conditioner Logo

Related Topics:

408 people viewed this question

Ask a Question

Usually answered in minutes!

Top DeLonghi Air Conditioners Experts

Michael Youngman
Michael Youngman

Level 2 Expert

156 Answers

Sudeep Chatterjee
Sudeep Chatterjee

Level 3 Expert

3267 Answers

Mike

Level 3 Expert

4331 Answers

Are you a DeLonghi Air Conditioner Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...