Question about MGE UPS Galaxy 3000 UPS System

2 Answers

Hello I have a problem on MGE Calaxy 3000 20KVA UPS. I change the batteries with new batteries when i put it on, the battery status deos not come just give me xxx . before has this erorr "UPS TEMPERTURE Fault" But I clean the Cooling Circle. and now it is ok. just the battery status deos not come means discharging. if i take AC IN off it will shut off in 1-2 minutes

Posted by on

2 Answers

  • Level 1:

    An expert who has achieved level 1.

  • Contributor
  • 1 Answer

I have a galaxy 3000.with 24 batteris and they are dead ,when i check Dc float is 270V that gives me 27 batteries .shoul i put 24 as it was or 27 to accomodate the float voltage

Posted on Sep 06, 2011

  • Level 1:

    An expert who has achieved level 1.

    New Friend:

    An expert that has 1 follower.

    Corporal:

    An expert that hasĀ over 10 points.

    Mayor:

    An expert whose answer gotĀ voted for 2 times.

  • Contributor
  • 14 Answers

The Galaxy 3000 uses a software which has all the data of the batteries used for the commissioning. However if the battery replaced are not of the same specification then the XXX would appear, meaning the software cannot match the specifications. Please try for first principle, check the ac in, check the rectifier and so on. Across the battery circuit breaker (in off position) compare the battery voltage and the charging voltage. This would give you an indication if the charger is working.

Posted on Apr 08, 2011

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Hello, our MGE GALAXY 3000 20kva, front panel display is frosen. UPS still operates but not able to use any buttons to see ups status. Also alarm states "internal communication fault". Would appreciate...


you need an MGE expert engineer to check on the internal components, maybe the display by itself it dead can be replaced while UPS is on no problem. if you want to switch off the UPS you go for force shutdown but I cannot guarantee will restart if you do not fix the fault.

Aug 09, 2013 | MGE Galaxy 3000 UPS System

1 Answer

Hello my UPS MGE 850 evolution is just blinking a red alert and does not charge even when conected to the power suply.. What could be the problem??


Battery has drained and gone.
Get new battery here http://www.battery-direct.com/ups/MGE-Evolution-MGE-EV850R.html

Please rate if this solved your problem.

Apr 19, 2011 | MGE Evolution 850 (68453) UPS System

1 Answer

Mge ellipse ups 1200 wont turn on/power up


hello, ik got a lot of these UPS for repair. I exclude any battery problem that I suppose you already checked. The Systems I have here does all have problem at charger electronics (VT 9 or components around) mostly burned out (short circuit). No repair is possible as copper lines are burned.

Apr 05, 2011 | MGE UPS Pulsar Ellipse 1200 UPS System

2 Answers

Mge galaxy 3000 how to reset battery expire alarm after battery change


Unfortunately the reset is only possible with MGE software (Softunor).

Jan 24, 2011 | MGE UPS Galaxy 3000 UPS System

1 Answer

Hello, could you please tell me the battery type of this UPS model in order to change it? Thank you.


12V (Per Cell)

6Ah

Dimensions

151mm x 94mm x 51mm (Per Cell)
Sealed Lead acid battery - you need 2 of these!

Oct 05, 2010 | MGE UPS Pulsar Ellipse Premium 800 UPS...

1 Answer

Hello, could you please let me know the battery type of MGE premium ellipse pulsar 800VA ups? Thanks in advance.


The batteries in an UPS are sealed lead acid batteries. The voltage and amp hour rating depends upon the VA rating of your UPS.
I suggest you shut down your UPS and remove the batteries and get replacement ones that are the same rating as the ones in the UPS. Be careful of the size of the battery, they are a neat fit inside the UPS battery compartment.

Oct 05, 2010 | MGE UPS Pulsar Ellipse Premium 800 UPS...

1 Answer

Hello Ive got cooling fault on my galaxy 3000 can u help


try to check the fluid in the cooling system, if it's full. then try to check the sensor on the cooling cap, or maybe change the sensor. Hope this help.
ps: cooling liquid is not water ( buy it from mge, i forgot what's the name )

Sep 04, 2010 | MGE UPS Galaxy 3000 UPS System

2 Answers

Mge pulsar 3000 does not power up


MGE Pulsar 3000 is an online UPS. try to check the battery first if its ok. coz for an online UPS it will need to have a good working UPS battery to trigger the switching relays to on the online UPS unlike backups UPS that can be turn on without any batteries

Aug 13, 2009 | MGE UPS Pulsar Evolution 3000 UPS System

1 Answer

MGE Galaxy 3000 UPS shows charger internal fault .


mge galaxy 3000 battery circuit breaker shut off when normal power shut off too.plz help !!!!!!

Jul 29, 2008 | MGE Galaxy 3000 UPS System

Not finding what you are looking for?
MGE UPS Galaxy 3000 UPS System Logo

Related Topics:

417 people viewed this question

Ask a Question

Usually answered in minutes!

Top MGE Computers & Internet Experts

yadayada
yadayada

Level 3 Expert

75077 Answers

Raj Patel

Level 3 Expert

899 Answers

Doctor PC
Doctor PC

Level 3 Expert

7733 Answers

Are you a MGE Computer and Internet Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...