I know that it's easy to spend someone elses money but in my experience when you get one actig that erratic it's usually the control board. I would check all the wiring including thermostat. You never know you might get lucky. I hope this helps you. Thanks
Thanks. So far I jumped the thermostat on the board itself and jumped the contacts on the limit switch and replaced the hot surface ignighter. ground looks good no corosion etc. Still have the same problem. FWIW 9 blinks code is check ignighter or possible ground problem.
I have the same problem, except mine works great while plugged into city power, however when I lost power and plugged XR80 into the 4000 watt generator, same results you have, What fixed yours?
×