1 Answer

Pressure of Ariston Microporus 27 MFFI

I have an Ariston 27 and I do not know which are the min and maximun pressure in bars that should be working the boiler when the radiators are hot and the bolider is working.

Posted by on

  • Anonymous Mar 28, 2014

    I have an Ariston pro eco 80v 2k boiler and while it's heating the preasure inside gets very high and the valve is leaking.is that something wrong with the boiler or it's only the valve broken?

×

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    Corporal:

    An expert that hasĀ over 10 points.

    Mayor:

    An expert whose answer gotĀ voted for 2 times.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 7 Answers

The boiler reqs to be pressurised to 1 bar in a cold state, in operation the heat expansion with cause the gauge to rise by about half a bar so in full working mode with heating on you'll expext the gauge to register around 1 1/2 bar-

Posted on Sep 18, 2008

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Does anyone know about ariston microcombi 23 mffi boilers


I know that but don't know how to get it bk down n don't really want to mess about with it it's all turned off just now anyway thanks xx

Nov 06, 2011 | Combi Centre DX - Mango

1 Answer

Ariston Microgenus 27 boiler - leaking motorised valve


The leak is coming from a seal around the pin that the motor acts upon, the seal does not come as a replaceable part on its own, so the whole flow group as it is called will need to be replaced, approximate price 170 to 200 pounds inc vat, makers part no 998613. plus 2 or 3 hours labour of a corgi registered engineer. If your boiler is more than 6 years old and you have not had to replace the fan or other parts yet, then think about getting a new high efficiency boiler, it could be a better long term solution.

Feb 15, 2009 | Combi Centre DX - Mango

1 Answer

Boiler losers pressure


make sure the heating is off and rads are cold before checking for leeks if pressure still drops chech expansion vessel is charged to 1 bar.

Jan 05, 2009 | Combi Centre DX - Mango

1 Answer

MicroGenus27 No Hot Water


check HW and CH temperature probes check secondary heat exchanger for blockage check water pressure switch

Jan 03, 2009 | Combi Centre DX - Mango

1 Answer

Boiler flames extinguish and reignite regularly


what about flame rectification probe (flame proving probe)

Nov 30, 2008 | Combi Centre DX - Mango

1 Answer

Ariston Microgenus 27mffi combi boiler


im an engineer and recently had exactly the same thing with this ariston boiler, i found out it was the the 'air pressure switch', this is a switch which is part of the ignition, it works in conjuction with the fan. when the boiler fires up the air pressure switch makes, if its faulty it can break the circuit mid flow and cause the burner to shut down therefore giving intermittent hot water and heating, theres a possibility that the aps tubes may be damaged as well so ensure they'e condition is good. hope this helps you

Aug 29, 2008 | Combi Centre DX - Mango

2 Answers

Ariston combi boiler


sounds like your diverter valve is passing on the boiler, this diverts the heat either to the rads or to the taps, if its passing through the heating chanel it'll heat up the rads- may also be a scaled up secondary heat exchanger, hope this helps you

Aug 21, 2008 | Combi Centre DX - Mango

1 Answer

Ariston microgenus 27 pressure on 0


Filling loop is underneath the boiler, easily identified as a chrome coloured braided pipe with a black tap at either end. Open right hand tap first then left hand one . Fill system till presure gauge reads just over 1 bar when system is cold. Then turn both taps off.

Jul 08, 2008 | Combi Centre DX - Mango

2 Answers

Gushing Water


sounds like youve topped the pressure up too much, the boiler needs to be on 1 bar pressure from a cold state, thats the max really you want to increase it too, in operation the boiler pressure increases due to heat expansion but sounds like you may have more of a problem, if your renting the property then its the landlords duty to ensure your boiler works and its safe- consult the landlord asap and they sohould help you out

Apr 21, 2008 | Combi Centre DX - Mango

Not finding what you are looking for?
Combi Centre DX - Mango Logo

Related Topics:

191 people viewed this question

Ask a Question

Usually answered in minutes!

Top Combi Baby Gear Experts

Stephen Faulkner
Stephen Faulkner

Level 2 Expert

541 Answers

Jennifer Rock
Jennifer Rock

Level 2 Expert

105 Answers

kakima

Level 3 Expert

98608 Answers

Are you a Combi Baby Gear Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...