Motor for Air handler will not stay on.

Hi there,

I have a Goodman Air handler and I replaced the motor last year. I noticed last night that the motor was starting, running for 2 seconds, shutting off, and then restarting every 30 seconds for the 2 seconds and then repeating. Please help! It's hot in Dallas Texas today!

Thank you,
Gabe

Posted by on

1 Answer

  • Level 2:

    An expert who has achieved level 2 by getting 100 points

    MVP:

    An expert that gotĀ 5 achievements.

    Champion:

    An expert who has answered 200 questions.

    Governor:

    An expert whose answer gotĀ voted for 20 times.

  • Expert
  • 254 Answers

Sounds to me lik eyou may have a bad run capacitor. this will most likely be an oval shaped device directly wired into the motor. Be very cautious when you remove this and make sure you discharge it to a grounding source as it will shock you.

Posted on Jun 12, 2008

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

I had a 2 ton 13 SEER air handler installed last August to replace one about 27 years old. The condenser was installed about 14 years ago and it's rated as a 10 SEER. Is there a problem of them operating...


The air 'handler' is nothing more than a type of fan turned by a motor.
The condenser however is a sealed, closed system with coolant that will need to be properly removed (EPA stuff). The condenser must be installed with care, recharged, then checked for leaks.
There is far more involved than replacing an air mover.

I do most of my repairs myself but sealed systems that must be charged is something I leave up to a pro.

Feb 14, 2015 | Goodman Heating & Cooling

1 Answer

Broken motor mount


they make a band mount to replace it with.

May 05, 2013 | Goodman Heating & Cooling

2 Answers

Unit exactly one year old. Was interruped by lightning strike last night. Afterwards air handler blowing, but not cooling? Turned unit of at temostat, waited a few minutes, turned back on and unit (both...


Marion, if there was a lightning strike and then a power surge when the power came back ON, I don't doubt what the servicemen had to say. The age of the unit plays no role in it, when something like this happens. Power surges can be killers to electrical appliances. That's why it always wise to turn the unit off during a power outage. Just ask anyone who was in Irene's path a couple of weeks ago. Power went out for days & weeks for some, when it came back ON, electrical appliances were damaged or ruined or started house fires.

Hope this helped you and thanks for choosing FixYa.

Sep 19, 2011 | Amana Heating & Cooling

1 Answer

I have a Goodman AR36-1 air handler. when I turn on the AC or the heat the air handler motor comes on for about a minute or two and then shuts off. The heat pump continues running and I can hear the air...


Hello Your motor is shutting of thermal overload because of an internal problem.New motor time,Pull it and match it up the info is on the side of the motor.

Oct 05, 2010 | Goodman Heating & Cooling

1 Answer

I have a 6 year old Goodman ClJ24. Today I noticed that the motor in the unit was running backwards.Instead of blowing out hot air from the top, it was sucking in air. Also unit suddenly is not cooling.


Hi,
Yes, once in a while the motor will just start to run in reverse...this is not fixable... you will need to replace that motor...and as you can see if it is not running correctly you will not get proper cooling...

Here is a tip about troubleshooting your air conditioner...
There are many things that can cause your air conditioner not to cool...

Air Conditioner Trouble - Review the Possibilities

heatman101

Sep 15, 2010 | Goodman CKL24AR24 Air Conditioner

1 Answer

Furnace unit to be louder now than last season


Check your air filter, make sure all registers are open full and there is no restriction in all ducts. Could be an unbalanced fan, clean the squirll cage fan with a brush and vacuum.

Jan 09, 2010 | Heating & Cooling

1 Answer

I have a Jantrol heat pump & A/C. It is approximately 10 years old. For the last 3 summers the compressor unit will freeze when the air handler fans fails to come on. It worked fine for 2 weeks this...


Hi,

If you can safely check the supply to the motor when it should be on, then this is the best method to check it.

Check the fan turns very freely - oil the bearings if it doesn't.

If there is power there, but it does not turn, replace the run capacitor.

If this get's you going - Please rate as Fixya so others may benefit. Thanks!

Jun 26, 2008 | Goodman Heating & Cooling

Not finding what you are looking for?
Heating & Cooling Logo

Related Topics:

124 people viewed this question

Ask a Question

Usually answered in minutes!

Top Heating & Cooling Experts

paulcarew

Level 3 Expert

2364 Answers

Dan Webster
Dan Webster

Level 3 Expert

8205 Answers

Donni Steen

Level 3 Expert

659 Answers

Are you a Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...