Question about MGE Galaxy 3000 UPS System

2 Answers

I had problem with my MGE Galaxy 30KVA. The problem is batt temperature fault and now the UPS status is not protected. I have tried to restart the UPS but the error still shown and cannot be deleted. Please help

Posted by on

Ad

2 Answers

  • Level 1:

    An expert who has achieved level 1.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 6 Answers

I hope you check all your batteries, to make sure they are fine. Also temp of room should be around 70 degree f. Check to make sure batteries are not over 3 years old... Might need replacement. Batt temp is a serious alarm.

Posted on Dec 11, 2011

Ad
  • Level 1:

    An expert who has achieved level 1.

    Mayor:

    An expert whose answer got voted for 2 times.

  • Contributor
  • 2 Answers

I have a temperature fault in my galaxy 3000. Try to clean the radiator behind the cabinet with the air compresor and clean all the fan inside so air circulation is good. Don't know about batt temperature fault. Hope this help.

Posted on Dec 03, 2010

Ad

3 Suggested Answers

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
New users get 2 Free calls (no credit card required) and instant help on almost anything you can think of (from cars to computers, appliances, handyman, and even pets).
click here to download the app (for users in the US for now) and get all the help you need.
Goodluck!

Posted on Jan 02, 2017

micromend
  • 748 Answers

SOURCE: mge galaxy 20kva ups input breaker trip

Does it trip immediately or after a time? If it's immediate then there's a dead short on the line (or possibly inside the UPS). If it takes time to trip then there's a slow build up of too much current use. This is usually caused by defective capacitors in a power supply.

Posted on Apr 06, 2009

  • 1 Answer

SOURCE: I have an MGE Galaxy 3000 15KVA which i replaced the batteries.

This is Easy,

MGE software is exclusive to them, they do this so that in the event the UPS needs any work you have to use them for remedial work, the problem is because they hold the monopoly they charge through the roof for parts and labour. you will need a factory trained engineer to turn up with a laptop to switch off the "Maintenance Alarms" I have an engineer that has the Software and availabilty to parts and we are much cheaper than MGE direct.

if you need any UPS help contact Glenn Prince @ Adept Power Solutions Ltd 01264 326726 or go to website www.adeptpower.co.uk

Posted on May 13, 2010

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

What batteries go in this unit how many 12? need a replacement


8.3 Battery Configurations

There are different configurations for different battery types and backup time. Here, the batteries from VISION and

YUASA are selected. The backup times ranges from 1hours to 4hours for 20KVA UPS and from 1hours to 2hours

for 30KVA UPS, because of limitation of CLA power rating.

UPS Backup

time Number of blocks Type of blocks Capacity(10H)

1h 1×24 6FM55SGX 52Ah

10kVA 2h 2×24 6FM45X 2×42Ah

4h 2×25 6FM75X 2×74.5Ah

1h 24 6FM75X 74.5Ah

15kVA 2h 3×24 6FM45X 3×42Ah

4h 3×25 6FM75X 3×74.5Ah

1h 1×25 6FM90X 90Ah

20kVA 2h 3×25 6FM55X 3×52Ah

4h 2×26 6FM150X 2×144h

1h 2×25 6FM75X 2×74.5Ah

30kVA

2h 3×24 6FM100X 3×96Ah

Sheet. 4 the battery configuration with VISION battery

UPS Backup time Number of

blocks Type of blocks Capacity

(10H)

1h 2X24 NPL24-12 2X24AH

10kVA 2h 2×26 NPL38-12 2×35.3AH

4h 2×26 NPL65-12 2×60.5Ah

1h 1×27 NPL65-12 60.5Ah

15kVA 2h 2×24 NPL65-12 2×60.5Ah

4h 3×26 NPL65-12 3×60.5Ah

1h 1×27 NPL100-12 92Ah

20kVA 2h 2×24 NPL100-12 2×92Ah

4h 4×26 NPL65-12 4×60.5h

1h 3X24 NPL65-12 3×60.5Ah
30kVA

Mar 30, 2014 | MGE Galaxy 3000 UPS System

1 Answer

GE LP33 30KVA output power fails when main goes out


if INVERTER IS ON, WHEN MAINS GO OFF IF UPS FAILS AT THE SAME MOMENT YOU NEED TO REPLACE ALL BATTERY SET

Feb 27, 2014 | MGE Galaxy 3000 UPS System

1 Answer

Hello, our MGE GALAXY 3000 20kva, front panel display is frosen. UPS still operates but not able to use any buttons to see ups status. Also alarm states "internal communication fault". Would appreciate...


you need an MGE expert engineer to check on the internal components, maybe the display by itself it dead can be replaced while UPS is on no problem. if you want to switch off the UPS you go for force shutdown but I cannot guarantee will restart if you do not fix the fault.

Aug 09, 2013 | MGE Galaxy 3000 UPS System

1 Answer

Temperature fault. Q5N open


pls cheak by pas slecter not normal position load on by pas temperature fault 1st cheak coling water 2nd room temp 3rd cheak temperature sencer battary breakr to batt bank side 2 wair

Jul 25, 2013 | MGE UPS Galaxy 3000 UPS System

1 Answer

Temperature fault


What is the temperature around the batteries?

Jul 25, 2013 | MGE UPS Galaxy 3000 UPS System

1 Answer

Galaxy 3000 30kVA not showns "battery charge"?


I can help you with this issue. Can you please give me some more information? What is the actual alarm saying? I know these UPS systems quite well

Sep 13, 2011 | MGE Galaxy 3000 UPS System

1 Answer

Galaxy 3000 30kVA showns battery charge fault.beacause battery?


UPS battery must be tested individually before you can decide it is a battery problem or if charging fault can cause by defective rectifier/charger board.

Sep 09, 2011 | MGE Galaxy 3000 UPS System

1 Answer

I want to know power supply of bypass ups MGE 30kva


Your question is very vague. Please restate it

Aug 24, 2011 | MGE UPS Pulsar EXL UPS System

1 Answer

MGE Galaxy 3000 UPS shows charger internal fault .


mge galaxy 3000 battery circuit breaker shut off when normal power shut off too.plz help !!!!!!

Jul 29, 2008 | MGE Galaxy 3000 UPS System

Not finding what you are looking for?
Computers & Internet Logo

Related Topics:

557 people viewed this question

Ask a Question

Usually answered in minutes!

Top MGE Computers & Internet Experts

yadayada
yadayada

Level 3 Expert

76630 Answers

Jax Planet
Jax Planet

Level 2 Expert

922 Answers

Raj Patel

Level 3 Expert

916 Answers

Are you a MGE Computer and Internet Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...