1 Answer

Compressor won't start - Bryant 462AJC021BA Air Conditioner

Posted by on

Ad

1 Answer

  • Level 3:

    An expert who has achieved level 3 by getting 1000 points

    Superstar:

    An expert that got 20 achievements.

    All-Star:

    An expert that got 10 achievements.

    MVP:

    An expert that got 5 achievements.

  • Master
  • 43,501 Answers


Hi,

Here is a tip about troubleshooting your air conditioner...
There are many things that can cause your air conditioner not to cool…

Air Conditioner Trouble - Review the Possibilities

heatman101

Posted on Sep 02, 2010

Ad

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of.(from cars to computers, handyman, and even drones)
click here to download the app (for users in the US for now) and get all the help you need.
Goodluck!

Posted on Jan 02, 2017

Ad

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Why my A/C condenser fan won t stop running, dodge ram 2008


To clarify, the compressor and fan will run in defrost mode. The compressor and fan runs to dry out the air blowing onto the windshield.
Now if the condenser fan runs in "heat" you may have a problem with the fan relay or the main controller.

Sep 25, 2014 | 2008 Dodge Ram Pickup 1500

Tip

Checking out a air conditioner compressor and compressor problems FIRST...


Checking out a air conditioner compressor and compressor problems
FIRST DISCONNECT ALL ELECTRICAL POWER
Ohm the windings
C to R = example 1.2
C to S = example 3.2
R to S = example 4.4 total of C to R and C to S or very close.

Then ohm each terminal to ground you shouldn't get any reading
If the compressor is hot or you tried to start it, the ohms will be close but not exact.
No reading from C to R or C to S open winding or thermal overload.
Let compressor completely cool down then ohm the C to R and C to S again
If it’s an open overload, you will get an ohm reading after it cools down and the overload closes,
you may just need to add refrigerant.
No reading from R to S and C to S open start winding.
In case of any open windings the compressor will have to be replaced.
If the compressor is getting the proper voltage and won’t start, it could be locked up.
You need an Ammeter to check this to see if it’s drawing locked rotor amps (60 amps or above)
You also need to check the run and start capacitor.
A bad run or start capacitor, the compressor won’t run, it will just hum.
If the compressor will run, but quits after a while and all of the above checks out OK.
It could be drawing high amps ( you will need an ammeter to check this out). Dirty condenser or condenser motor not running, overcharge of refrigerant, shunted windings, bad bearings in compressor.
The compressor gets hot and Suction or big line coming in to outdoor unit is warm or slightly cool, you are low on charge or metering device bad or stopped up.
If compressor runs for a while and quits and the suction line is frozen, cold or cool, then the filter, evaporator or condenser coils are dirty or plugged up, blower or fan motor not running and unit going off on high or low pressure switches.

on Dec 29, 2009 | Heating & Cooling

1 Answer

Ac fan not running, but compressor runs on and off


switch/ fuse possible if it has one, if not one of the wire going to the motor was severed, or the start up capacitor of the motor if it also has one.

Jun 04, 2013 | Frigidaire FAX054P7A Wall/Window Air...

1 Answer

The compressor won't stop running


Sounds like the contacs on thermostat, has welded togher. Compressor will run till it starts pumping liquid frezon, then over heats ,then shuts down till it cools off , and starts all over again
replace thermostat..

Jan 13, 2013 | Refrigerators

1 Answer

Compressor won't come on


if you have power, the pressure switch is stuck or bad.

Jan 11, 2013 | Coleman Powermate 11 Gallon Air Compressor

1 Answer

Compressor won't start after cycle


Capacitor if capacitor start, sticky relay or faulty compressor if not.

May 19, 2012 | Kenmore Top Freezer Refrigerator

Not finding what you are looking for?
Bryant 462AJC021BA Air Conditioner Logo

Related Topics:

107 people viewed this question

Ask a Question

Usually answered in minutes!

Top Bryant Heating & Cooling Experts

christian nielsen

Level 3 Expert

358 Answers

Dan Webster
Dan Webster

Level 3 Expert

8220 Answers

Bill Long

Level 3 Expert

587 Answers

Are you a Bryant Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...