1 Answer

Do bryant condensing units have a reset button? We can't get the unit to kick on. All power is correct and fan starts inside, but can't get condensing unit to kick on.

Posted by on

1 Answer

  • Level 2:

    An expert who has achieved level 2 by getting 100 points

    MVP:

    An expert that gotĀ 5 achievements.

    Governor:

    An expert whose answer gotĀ voted for 20 times.

    Hot-Shot:

    An expert who has answered 20 questions.

  • Expert
  • 107 Answers

Most Bryant units do not have a reset button but could have a low pressure or high pressure switch for a safety to protect the compressor. Verify power from the thermostat to the contactor by following the thermostat wires all the way to contactor inside of electrical compartment... TURN POWER OFF BEFORE OPENING.... If power is to contactor and contactor is pulled in then you would need to look at the capacitor of which is a canister about 6 inshes tall with wire terminals on top.. this part should be flat on the top and if it is rounded then thats your problem.. if not then contact a local company to troubleshoot and make necessary repairs.

Posted on Sep 01, 2010

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Bryant plus 90


try replacing the run capacitor

Sep 03, 2013 | Heating & Cooling

1 Answer

Fan wont kick on


a bad fan motor they will go bad is the blower on your inside unit or the condenser assembly outside either could be a bad motor

Jul 13, 2012 | Intertherm Heating & Cooling

1 Answer

My fan is nto blowing on my outside unit. i hear a light hum coming from the unit.


Sounds like the contactor is pulled in, but no power to the condenser fan motor. Check power to motor (through the contactor & check the capacitor.

Jul 11, 2011 | Bryant 463AAC008BA Air Conditioner

1 Answer

Fedder Heat Pump not Running


you can check your heat pump on the outside by turning off the power and listening to see if it makes a whoosh sound. and then turn it back on you should hear it kick in. Is the outside unit running? Sounds like an electrical problem maybe in the breaker or the contactor on the inside of the unit. This is where the 24 volts from the thermostat call to the 240 volts to kick on the condenser fan and compressor. Be real careful in messing with this because of the high voltage.

Jul 09, 2010 | Fedders C36ACD1VF Split System Air...

1 Answer

Condenser the compressor vibrates bad and then it shuts down code on board says high thermal cutoff


Hi, what is happening is the unit is shutting off on high head pressure from the sound of it. Bryant units are top of the line! What you need to do is shut the main power off to unit. I dont no if you have a split system 2-part with a indoor unit and outdoor unit or a package unit all in one. It really makes no difference. Go to the outdoor coil, which is the condenser coil. Take a good water hose and wash this coil very good all around and inside where the fan motor is. These units are made for outdoor use but don't spray directly on the controls. Be careful not to mash the fins with to much pressure.If the fan motor outside is running up to a good speed, this will take care of the high head pressure, I know for a fact. Let me know the out come. If by some reason it does not cure this, we will go into it further. I will be waiting to hear from you.
Sincerely,
Shastalaker7

Jun 03, 2010 | Bryant 463AAC008BA Air Conditioner

2 Answers

Bryant air condition fan outside not coming on


Check breaker for outside unit Also check to see if you ahve afloat switch on the inside air handler. Located under or in front of unit. It may be full of water and tripped. Blow out drain if tripped.

Jun 15, 2009 | Ruud UBHC Air Conditioner

1 Answer

Bryant central air unit fan doesn't stop.


This is a condenser fan and as long as the A/c unit is in cool mode, this fan will run. The only time it should shut off is when temperature setting is satified and the unit shuts off.

Jun 03, 2009 | Heating & Cooling

1 Answer

Condenser unit will not come on


Replace the starter capacitor.

Apr 27, 2009 | Bryant Heating & Cooling

Not finding what you are looking for?
Heating & Cooling Logo

805 people viewed this question

Ask a Question

Usually answered in minutes!

Top Bryant Heating & Cooling Experts

christian nielsen

Level 3 Expert

358 Answers

Dan Webster
Dan Webster

Level 3 Expert

8220 Answers

Mike Squire

Level 2 Expert

391 Answers

Are you a Bryant Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...