I have a new chandelier with 9 12 volt halogen bulbs. I want to install an electronic dimmer switch for it. When purchasing the dimmer switch there are 4 wires included: ground, black, white and neutral. In the light switch box there are only the 3 wires: ground, black and white - no neutral. Due to the transfer of energy specifications, is the only way to connect the neutral wire by feeding a line through the walls from the ballast of the chandelier to the light switch box? Is there any way I can just connect the neutral wire to the ground wires? Thanks for your suggestions. I have searched everywhere without luck.

Posted by on

Ad

1 Answer

  • Level 3:

    An expert who has achieved level 3 by getting 1000 points

    All-Star:

    An expert that got 10 achievements.

    MVP:

    An expert that got 5 achievements.

    Vice President:

    An expert whose answer got voted for 100 times.

  • Master
  • 760 Answers

First you must have a neutral wire in the switch box for this dimmer to work. A neutral wire (white) is a current carrying conductor. A ground wire is an equipment ground and does not normally carry current. You should never connect a device that requires a neutral to a grounding conductor.
The neutral wouldn't have to come from the light fixture as long as it's on the same circuit. Another note is to check your light fixture, and be sure dimming is ok. Another choice you could have is to install a remote dimming device. You would mount this in the fixture canopy, and then use a remote dimmer.

Posted on Aug 03, 2010

Ad

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Ad

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Switch doesn't work


Because the switches have electronics in them the ground wire may be very important to give it a full 120 volts to be able to run. Also double check your lighting, these dimmers are likely for incondescent lighting only (light bulbs). A compact fluorescent or some other lighting may blow the switches. If your lights are led they may not have sufficient resistance so that the dimmer knows that you have any lighting at all. Fluorescent lighting has to high a capacitive reactance and or inductive reactance. Halogen or other lights may cause troubles too. Check the directions on your switches to see if they were for incondescent only or for fluorescent only etc. Also modern bulbs don't seem to screw far enough into the sockets because of their fat necks that bottom too soon. You may have to turn off the power then put your finger inside to bend the bottom contact up enough to touch the bulbs.

May 04, 2013 | Cooper Wiring Devices Aspire Dimmer...

1 Answer

I have always used a lutron maestro dimmer. I replaced the chandelier and put in 6-60 watt bulbs. My previous chandelier used 18-25 watt chandelier bulbs and the dimmer worked fine. after changing the...


You should have just two wires plus a ground hooked up to the dimmer. It should install just like the maestro. If you are getting no lights with a double tap, or tap and hold, and if the led is not on, it is one of several things. Most are basic, but will list anyway. Check that your connections are good. Make sure you have power there. Make sure the bulbs are good. If all is fine, you probably have a defective dimmer if it worked prior to this. To test, take the dimmer out, restore power, and carefully touch one insulated wire to the other one. If the light comes on, it is the dimmer at fault.

Mar 06, 2011 | Lutron ELECTRONICS MAW-600H-LA SMART...

1 Answer

Removed the switch plate and connected the two wires going into the dimmer box and the lights still dont come on. I as thikning by bypassing the dimmer the lights should still function. What else could be...


Hi Jay,
Ive suspect that there's a problem in the main line of the wiring. Since four halogen bulb are already replaced with a new bulb and bypassed the dimmer switch concentrate now on the wiring and the main panel board. Look for a tripped/busted breaker on the box, reset it.Replaced if busted. If nothing works, you need to check the wiring on the ceiling for open.
Hope it may help you.
Have a nice day!
Thanks for using fixya.
JDVillanueva

Feb 04, 2011 | Lutron ELECTRONICS MAW-600H-LA SMART...

1 Answer

Removed the switch plate and connected the two wires going into the dimmer box and the lights still dont come on. I as thikning by bypassing the dimmer the lights should still function. What else could be...


I am going to stick my neck out a little with this one although I agree with BoomerP. The clue of halogen bulbs is feeding my answer. Halogen bulbs require a high voltage transformer to operate and won't normally work with a dimmer but I never tried it. Bypassing the switch should bring them on though. If you have the proper voltage at the switch and they don't work with the switch bypassed, its probably a bad transformer in the fixture. Good Luck. Be careful.

Feb 04, 2011 | Lutron ELECTRONICS MAW-600H-LA SMART...

1 Answer

I just installed a chandelier. This is a new connection. So I ran a 3 wire from the chanderlier to a new lutron slide dimmer. I then ran a 2 wire from this dimmer to the switch. When I turned the...


Lutron Dimmer manuals
http://www.lutron.com/Service-Support/Technical/InstallationInstructions/Pages/InstallationInstructions.aspx?syst=Dimmers+%26+Switches&prodn=Maestro%C2%AE+dimmer+%26+switch

Lutron manuals show a couple things that might be affecting you lights.
1) Wattage: If you have wrong wattage dimmer
2) Type of light bulb: Dimmers work on different types of bulbs
3) Wiring: You say you got 3 wires going to the chandelier? Why you got 3 wires? Is this a 3 way switch? Are the chandelier bulbs wired separately so you can control groups of bulbs with different switches?
Does the dimmer have 3 screws? A dark-colored screw and 2 brass screws? If so, then that sounds like a 3-way dimmer. A 3-way, is where more than one switch controls the same light.

Does the dimmer have 2 screws? Then that dimmer controls a single circuit. Your black Hot wire from breaker box connects to one screw and the black wire to Load connects to other screw.
A quick glance at Lutron wiring manual shows that Hot and Load wires connect to either screw.
The question is your 3-wires from the chandelier ... does the black Hot wire from breaker arrive in the ceiling box first? Or does it arrive in the wall box first? If your Hot arrives in ceiling box, then the Hot must come down to the switch box and connect to a screw on the dimmer >>> a second wire connects to other screw on dimmer and travels up to the ceiling box where it connects to black wire on chandelier. The white wire on chandelier connects to white Neutral.
4) Dimmer might be bad

Oct 16, 2010 | Lutron #DVW-603PGH-WH 600W White Single...

1 Answer

Apparent fixture problem for halogen plug


This dimmer was not made to dim a load smaller than 40VA. That halogen bulb would only have been 20VA or so.

http://www.lutron.com/cms400/PageBuyNow.aspx?id=16977&mn=1815

I think that when your bulb burnt out, the dimmer over-volted the transformer and smoked it. That said, I think you have a fixture problem and, possibly, a switch problem, too.

May 17, 2009 | Lamson HOME PRODUCTS AR180 "PLUG IN...

1 Answer

A fixture on a Lutron Maestro dimmer switch stopped working.


This dimmer was not made to dim a load smaller than 40VA. That halogen bulb would only have been 20VA or so.

http://www.lutron.com/cms400/PageBuyNow.aspx?id=16977&mn=1815

I think that when your bulb burnt out, the dimmer over-volted the transformer and smoked it. That said, I think you have a fixture problem and, possibly, a switch problem, too.

Mar 23, 2009 | Lutron Maestro 600-Watt Multi-location...

Not finding what you are looking for?
Electrical Supplies Logo

Related Topics:

155 people viewed this question

Ask a Question

Usually answered in minutes!

Top Electrical Supplies Experts

Steve

Level 3 Expert

3287 Answers

Gene Haynes

Level 3 Expert

5089 Answers

Brad Brown

Level 3 Expert

15667 Answers

Are you an Electrical Supply Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...