Question about Robinair Cool Tech 34700Z Recovery, Recycling, Recharging

1 Answer

ROBINAIR 347002K WON'T INJECT OIL

I HAVE A ROBINAIR COOLTECH 700 MODEL 347002K. THE OIL INJECT DOES NOT WORK, IT WAS WORKING UNTIL OIL INJECT WAS USED WITH VALVES IN THE RECOVER/VACUUM SETTING. PAG OIL BEING USED HAS UV DYE, WOULD EITHER CAUSE THIS PROBLEM?

Posted by on

Ad

1 Answer

  • Level 2:

    An expert who has achieved level 2 by getting 100 points

    All-Star:

    An expert that got 10 achievements.

    MVP:

    An expert that got 5 achievements.

    President:

    An expert whose answer got voted for 500 times.

  • Expert
  • 180 Answers

I think you'v try to inject the oil from ''WRONG'' side,as you say RECOVER/VACUUM which is LOW side manifold valve. You should inject the oil from HIGH side ( Turn the high side valve to CHARGE/OIL INJECT after vacuuming & low side vulv to CLOSE possition ) with pressing F1 key. once you press it then hold the key as long as you wish to inject the oil. If you try this way & you still have problem with oil injection then you may need to check oil injection CHECK VALVE or oil injection SOLENOID ( Both located under Hidg side panel mountin valve). NOTE: UV Dye is not a problem for oil injection! I hope this will help you to solve the problem,Good luck. Don't forge to vote for my solution!

Posted on Jul 10, 2010

Ad

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of.(from cars to computers, handyman, and even drones)
click here to download the app (for users in the US for now) and get all the help you need.
Goodluck!

Posted on Jan 02, 2017

Ad

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

WILL NOT INJECT OIL


No service manual?

What about support from the folks
you got it from--assuming it is in a shop?

Call Robinair

Jul 15, 2014 | Robinair Cooltech 34788 R134a Automatic...

1 Answer

We have a robinair cooltech 34700z, looking for directions to change pump oil, can anyone help? thanks


For change vacuum pump oil follow the bellow step: Press main menu then keep pressing up or down arrow key till display show "CHANGE VACUUM OIL" then press "YES" key. Now vacuum pump will run for two minute & stop automatically. When pump stop you just open the oil drain cap and drain all used oil from pump (oil drain cap located outside of the machine near high & low side hose). After draining all used oil replace oil drain cap and fill 5 ounce new ROBINAIR vacuum pump oil then press "YES" key and keep filling oil up to middle of sight glass of vacuum pump. Press "STOP" key to complete the process.

NOTE: Do not over fill the pump & do not use any COMPRESSOR oil on the vacuum pump!
Hope this will help you & if it is please vote for my support
.
Hope this will help you. If so please vote for it. Good luck

Apr 08, 2011 | Robinair Cool Tech 34700Z Recovery,...

1 Answer

I have a Robinair 347002K abnd cannot access anything under defaults. Defaults show as a menu item, but I can not see or select anything else under that heading I tried the 5454 password i saw on another...


You may did not try in the right way! The access code (5454) is 100% right for 347002K/347112K and 34700Z new series machines. If keypad has oil injection button (old series machine) press 8787 on keypad.
However you can try as following: To access the change Defaults menu press 5454 (If keypad has oil injection button old series machine press 8787) on the keypad then press ENTER/START arrow key. Now display will change to "Calibrate Scale". Press up or down key to select option you wish to access from: Set Tank Tare, Output Test, Input Test, Keypad Test. Prepare to Ship. Reset Board Memory etc...

NOTE: DO NOT CHANGE 'SET TANK TARE' OR PRESS 'PREAPARE TO SHIP' & RESET BOARD MEMORY' IF YOU ARE NOT FAMILIAR WITH THIS MACHIN!

Hope this will help you. Good luck!

Mar 31, 2011 | Robinair Cool Tech 34700Z Recovery,...

2 Answers

The high pressure unit is disabled in my Robinair Cooltech 34700z wat could be the problem?


This is a common problrm of Robinair 34700Z / 347002k & 347112k series machine.so don't worry just do the following :- 1# Verify the ISV tank is not overfilled.if full,remove refrigerant manually from tank. 2# Verify if there is high pressure in the tank.Purge excess air from the tank manually.( Open air purge hose from the tank,then press tank valve as needed) 3#Check the high pressure switch for proper operation,if not then replace high pressure switch.Hope this will solve your problem, if so please vot for it

Jan 04, 2011 | Robinair Cool Tech 34700Z Recovery,...

1 Answer

347002k. wants to inject oil in charge mode? is it the check valve?


You have to do Just following # Check oil drain solenoid for any debris or damage inside the solenoid flunger. Replace/rebuild as needed. Hope this will solve your problem. Don't forget to vote for my solution

Nov 18, 2010 | Robinair Cool Tech 34700Z Recovery,...

1 Answer

UNIDAD DE ALTA PRESION DESABILITADA ROBINAIR


This is a common problem of Robinair 34700Z / 347002k

Sep 28, 2010 | Robinair Cool Tech 34700Z Recovery,...

1 Answer

Wont clear filter


If the clearing the filter screen will not go off then it is sure that compressor is not good.please check the compressor with vacuum gauge & make sure is has 13" HG of suction.

Aug 12, 2009 | Robinair Cool Tech 34700Z Recovery,...

2 Answers

Source tank empty


You have to rebuild tank fill solenoid.Thank you.

Mar 26, 2009 | Robinair Cool Tech 34700Z Recovery,...

Not finding what you are looking for?
Robinair  Cool Tech 34700Z Recovery, Recycling, Recharging Logo

1,464 people viewed this question

Ask a Question

Usually answered in minutes!

Top Robinair Measuring Tools & Sensors Experts

Mike

Level 3 Expert

4340 Answers

Jay Finke
Jay Finke

Level 3 Expert

1363 Answers

Brad Brown

Level 3 Expert

16195 Answers

Are you a Robinair Measuring Tool and Sensor Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...