I have an Ariston Microgenus 27 Combi Boiler

Just recently this boiler has decided not to heat my radiators but still gives me plenty of hot water, the heating pipe coming from the pump is hot for about a foot and the pipe going back into the boiler is cold, can anyone advise me wether or not I should buy a new pump ( I have managed to price one up at about 72 Pounds inc VAT ) or would a better option be to buy a new boiler as I might just end up replacing worn out parts for the next couple of months. Thanks for any help

Posted by on

  • Anonymous Mar 28, 2014

    Have had lots of problems with this boiler.

×

1 Answer

I hate these boilers!

If the pump is not circulating change it. If the pump is ok you may have a blockage in the diverter valve

Posted on Jul 05, 2008

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Ariston microgenus he24 fault is e34 but boiler works when front cover is removed


e34 on a ariston is the fan. Boiler fires up with cover off as its getting the air it needs from atmosphere! fan is not running at full speed

Nov 04, 2011 | Combi Centre DX - Mango

1 Answer

My ariston micro genus type c boiler keeps going hot and cold, the heating also switches on and off, any ideas


when was it last serviced?dirt may be a factor,there are many parts that cause this fault in the microgenus so you need someone familer with the product parts playing up could be1.airswitch2motor3flowgroup4ntc you havent mentioned if it needs re-setting

Jan 10, 2010 | Combi Centre DX - Mango

1 Answer

Ariston Microgenus 27 boiler - leaking motorised valve


The leak is coming from a seal around the pin that the motor acts upon, the seal does not come as a replaceable part on its own, so the whole flow group as it is called will need to be replaced, approximate price 170 to 200 pounds inc vat, makers part no 998613. plus 2 or 3 hours labour of a corgi registered engineer. If your boiler is more than 6 years old and you have not had to replace the fan or other parts yet, then think about getting a new high efficiency boiler, it could be a better long term solution.

Feb 15, 2009 | Combi Centre DX - Mango

1 Answer

MicroGenus27 No Hot Water


check HW and CH temperature probes check secondary heat exchanger for blockage check water pressure switch

Jan 03, 2009 | Combi Centre DX - Mango

1 Answer

Boiler flames extinguish and reignite regularly


what about flame rectification probe (flame proving probe)

Nov 30, 2008 | Combi Centre DX - Mango

1 Answer

Ariston Microgenus 27mffi combi boiler


im an engineer and recently had exactly the same thing with this ariston boiler, i found out it was the the 'air pressure switch', this is a switch which is part of the ignition, it works in conjuction with the fan. when the boiler fires up the air pressure switch makes, if its faulty it can break the circuit mid flow and cause the burner to shut down therefore giving intermittent hot water and heating, theres a possibility that the aps tubes may be damaged as well so ensure they'e condition is good. hope this helps you

Aug 29, 2008 | Combi Centre DX - Mango

2 Answers

Ariston combi boiler


sounds like your diverter valve is passing on the boiler, this diverts the heat either to the rads or to the taps, if its passing through the heating chanel it'll heat up the rads- may also be a scaled up secondary heat exchanger, hope this helps you

Aug 21, 2008 | Combi Centre DX - Mango

1 Answer

Ariston microgenus 27 pressure on 0


Filling loop is underneath the boiler, easily identified as a chrome coloured braided pipe with a black tap at either end. Open right hand tap first then left hand one . Fill system till presure gauge reads just over 1 bar when system is cold. Then turn both taps off.

Jul 08, 2008 | Combi Centre DX - Mango

1 Answer

Pressure of Ariston Microporus 27 MFFI


the boiler reqs to be pressurised to 1 bar in a cold state, in operation the heat expansion with cause the gauge to rise by about half a bar so in full working mode with heating on you'll expext the gauge to register around 1 1/2 bar-

Jun 14, 2008 | Combi Centre DX - Mango

Not finding what you are looking for?
Combi Centre DX - Mango Logo

799 people viewed this question

Ask a Question

Usually answered in minutes!

Top Combi Baby & Toddler Car Seats Experts

paulcarew

Level 3 Expert

1875 Answers

Les Dickinson
Les Dickinson

Level 3 Expert

18298 Answers

Are you a Combi Baby and Toddler Car Seat Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...