Question about Combi Centre DX - Mango

1 Answer

I have an Ariston Microgenus 27 Combi Boiler

Just recently this boiler has decided not to heat my radiators but still gives me plenty of hot water, the heating pipe coming from the pump is hot for about a foot and the pipe going back into the boiler is cold, can anyone advise me wether or not I should buy a new pump ( I have managed to price one up at about 72 Pounds inc VAT ) or would a better option be to buy a new boiler as I might just end up replacing worn out parts for the next couple of months. Thanks for any help

Posted by on

  • Anonymous Mar 28, 2014

    Have had lots of problems with this boiler.

×

1 Answer

I hate these boilers!

If the pump is not circulating change it. If the pump is ok you may have a blockage in the diverter valve

Posted on Jul 05, 2008

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Ariston microgenus he24 fault is e34 but boiler works when front cover is removed


e34 on a ariston is the fan. Boiler fires up with cover off as its getting the air it needs from atmosphere! fan is not running at full speed

Nov 04, 2011 | Combi Centre DX - Mango

1 Answer

Ariston Microgenus 27 boiler - leaking motorised valve


The leak is coming from a seal around the pin that the motor acts upon, the seal does not come as a replaceable part on its own, so the whole flow group as it is called will need to be replaced, approximate price 170 to 200 pounds inc vat, makers part no 998613. plus 2 or 3 hours labour of a corgi registered engineer. If your boiler is more than 6 years old and you have not had to replace the fan or other parts yet, then think about getting a new high efficiency boiler, it could be a better long term solution.

Feb 15, 2009 | Combi Centre DX - Mango

1 Answer

MicroGenus27 No Hot Water


check HW and CH temperature probes check secondary heat exchanger for blockage check water pressure switch

Jan 03, 2009 | Combi Centre DX - Mango

1 Answer

Boiler flames extinguish and reignite regularly


what about flame rectification probe (flame proving probe)

Nov 30, 2008 | Combi Centre DX - Mango

1 Answer

COMBI BOILER /CENTRAL HEATING


the boiler should modulate to controll the radiator temperature but the central heating will go off whilst you are drawing hot water

Nov 13, 2008 | Water Heaters

1 Answer

Ariston Microgenus 27mffi combi boiler


im an engineer and recently had exactly the same thing with this ariston boiler, i found out it was the the 'air pressure switch', this is a switch which is part of the ignition, it works in conjuction with the fan. when the boiler fires up the air pressure switch makes, if its faulty it can break the circuit mid flow and cause the burner to shut down therefore giving intermittent hot water and heating, theres a possibility that the aps tubes may be damaged as well so ensure they'e condition is good. hope this helps you

Aug 29, 2008 | Combi Centre DX - Mango

2 Answers

Ariston combi boiler


sounds like your diverter valve is passing on the boiler, this diverts the heat either to the rads or to the taps, if its passing through the heating chanel it'll heat up the rads- may also be a scaled up secondary heat exchanger, hope this helps you

Aug 21, 2008 | Combi Centre DX - Mango

1 Answer

Pressure of Ariston Microporus 27 MFFI


the boiler reqs to be pressurised to 1 bar in a cold state, in operation the heat expansion with cause the gauge to rise by about half a bar so in full working mode with heating on you'll expext the gauge to register around 1 1/2 bar-

Jun 14, 2008 | Combi Centre DX - Mango

1 Answer

No hot water help


have a ariston euro combi boiler ,the problem to get hot water i have to turn the heating on to get hot water. but now it only run for a few min then run cold please help

Feb 18, 2008 | Washing Machines

Not finding what you are looking for?
Combi Centre DX - Mango Logo

802 people viewed this question

Ask a Question

Usually answered in minutes!

Top Combi Baby Gear Experts

paulcarew

Level 3 Expert

2430 Answers

Les Dickinson
Les Dickinson

Level 3 Expert

18386 Answers

ray gallant

Level 3 Expert

41139 Answers

Are you a Combi Baby Gear Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...