F22 error/ low pressure

My vaillant ecotec plus 824 boiler is showing an error code F22 and pressure is down nto 0.2 bar can you shed any light please?

Posted by on

1 Answer

  • Level 3:

    An expert who has achieved level 3 by getting 1000 points

    Superstar:

    An expert that got 20 achievements.

    All-Star:

    An expert that got 10 achievements.

    MVP:

    An expert that got 5 achievements.

  • Heating & Co... Master
  • 2,461 Answers

F.22 Dry fire Too little water in the appliance, water pressure sensor defective,
cable to pump or water sensor defective, pump blocked or defective,
pump output too low

Posted on May 12, 2010

Testimonial: "thank you so much the information supplied allowed a local plumber to fix our problem in minutes 10/10"

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Vaillant error F22


The water pressure is too low. Set it for 1.5 - 2.0 BAR.

Mar 05, 2014 | Computers & Internet

1 Answer

Boiler vaillant ecotec 824 R1 no power


USE A ELECTRIC METER AND CHECK FOR 120 VOLTS AT CIRCUIT BOARD AT LINE IN AND COMMON , IF YOU DO HAVE 12 0 VOLTS THE LOOK FOR TAPPINGS FOR 24 VOLT OUT PUT MAYBE A BAD TRANSFORMER OR CIRCUIT BOARD

Jan 11, 2014 | Water Heaters

1 Answer

My valliant combi boiler 4 years old wont start up fault code 22 flashes up


F22 means low water pressure. Check the pressure dial on the boiler and adjust using the link pipe and valves.

Nov 15, 2013 | Computers & Internet

1 Answer

Got a f.75 on boiler have to put pressure up to 2.0 bar before it starts


I take it this is a Vaillant EcoTec boiler? If your having to pressurise to 2.0 before the F75 goes, there's a strong probability there's a problem with the water pressure sensor. These can sometimes just have dirt/sludge in them, and can be cleaned, however a lot of the time they just need to be replaced. F75 can also mean there's a circulation problem through the boiler, and you will get the same fault code. If you have the old rubber hoses on the flow and return pipes, these can be prone to blocking/restricting and Vaillant have actually modified this part whereby by the pipes are solid copper.

Dec 04, 2012 | KDS Valiant 6380iPTD-01 Notebook

1 Answer

Have a ecotec 824 plus boiler the bar goes upto 2.7 and stays round 1.5 when not operating,what is causing this?


Sounds to me like the expansion vessel is not working correctly. When the boiler is on the water gets hot and expands into the expansion vessel but if the vessel is not working the pressure will rise and will eventually escape through the pressure relief valve.

Feb 18, 2012 | Computers & Internet

2 Answers

Lost my user manual for the vaillant boiler ecotec plus 824 R1


try to enter here all informations and you can find the manual: http://instructions-manuals.com/search.php?cmarque=VALLIANT%20&modele=ECOTEC%20PLUS%20824

Oct 27, 2009 | KDS Valiant 6380iPTD-01 Notebook

2 Answers

F22 on my vaillant boiler turbo max


Hi Guy's,
The answer is that your system is out of water pressure.
Usually there is a nob on the right under the base of the unit near to the small dial to the right of the front cover.
To enable the system to work correctly the needle on this dial should be in the Grey, about midway position.
Currently with fault F22 this will be lower to below the Grey and on the needle.
To bring the pressure back to the correct position, you need to turn this nob until you hear the water entering the system, KEEP AN EYE ON THE DIAL AND TURN THE WATER OFF AGAIN WITH THIS NOB ONCE THE DIAL IS IN THE CORRECT GREY POSITION AS MENTIONED ABOVE. DO NOT OVER FILL THE SYSTEM. I suggest you check this every six months or so.
Once this is corrected your unit will light up again.
Best of luck. Mike. N.

Feb 01, 2009 | KDS Valiant 6380iPTD-01 Notebook

Not finding what you are looking for?
Heating & Cooling Logo

Related Topics:

1,571 people viewed this question

Ask a Question

Usually answered in minutes!

Top Heating & Cooling Experts

paulcarew

Level 3 Expert

2461 Answers

Dan Webster
Dan Webster

Level 3 Expert

8220 Answers

Donni Steen

Level 3 Expert

659 Answers

Are you a Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...