I have a 5 ton Intertherm split unit. The compressor will kick off after 4 minutes of operation. Unit is blowing ampient air. I think it may be low on freon. Unit is 5 years old. What could be possible problem? Not sure what model it is. Data plate is missing.
Hi,
Here is a tip that will help you and at the bottom there are even more....
http://www.fixya.com/support/r3571569-air_conditioner_trouble_review_the_possi
heatman101
Very good possibility that it is low on freon. If indoor unit is blowing ambient air, not cooling is happening. If this is the case and you are sure the compressor is running and then shutting off, the compressor could be overheating and the internal overload is taking out the compressor. If outdoor fan runs and compressor runs, probably cause. If capacitor is bad, unit would most likely not run that long. While unit is running, feel the large line at the condensing unit. If it is cold, and stays cold, could be something else going on. If stays warm, most likely low on freon.