Indoor unit faults = CH04 or C4
Fascia LED's
- RED = None
- GREEN = 4 Flash
Contents = Drain Pump / Float Switch
Case of Error = Float Switch Open Circuit (High Level Water Alarm)
Indoor Status = Off
Yes they Do they are called Dual Zone Units. At http://www.paylessminisplit.com they are very helpful if you call them they can answer alot of questions about many brands of mini split air conditioners.
E-5 -Comms Error, check your wiring, remove external pumps. Split/Multi - check volts from terminal N to 3 = 0 - 65 Vdc, Multi V - 4 Vdc terminals 3 and 4
It depends on the (EER) Energy Efficiency Ratio,which is capacity divided by watts.
Example 35000 btus / 2500 watts = 14 EER
If you know the capacity,btus and EER you can calculate the watts, capacity / EER
Example 35000 btus / 14 EER = 2500 watts.
EER is determine by testing the air conditioner at Department of Energy Guidelines, which are
80° drybulb 67° wetbulb indoor and 95° and 82° drybulb outdoor.
×