50K BTU Reddy Heater Trips Circuit Breaker

My 50K BTU Reddy Heater Trips Circuit Breaker on the heater after about 30 seconds of running. Any idea of the cause?

Thanks

Posted by on

  • Anonymous Jan 18, 2008

    mine does the same thing-----it will run perhaps 30 seconds and trip the breaker

  • tythreatt Mar 02, 2008

    I FOUND THAT IT IS THE PHOTO CELL. I JUMPERED IT OUT. WHAT IS THE DANGER IF YOU NEVER RUN OUT OF FUEL?

×

Ad

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    Corporal:

    An expert that hasĀ over 10 points.

    Mayor:

    An expert whose answer gotĀ voted for 2 times.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 19 Answers

If the unit lights Check the photo cell this can be done with an ohm meter and good light. Should have continuity in light.

Posted on Mar 02, 2008

  • Todd Gibb Mar 03, 2008

    The danger is if it doesn't light it will keep pumping fuel creating a mess and fire hazard.

×

Ad

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
A 6ya expert can help you resolve that issue over the phone in a minute or two.
Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
The service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
Good luck!

Posted on Jan 02, 2017

Ad

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Runs about 30 seconds then cuts off . reddy 110 btu ?


Hi,


Here are a couple of tips that I wrote that tell you how to troubleshoot a Torpedo or Reddy heater...

Reddy Heater - Troubleshooting Torpedo Heaters





Torpedo Heater Pump Pressure Adjustment


heatman101


/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0/0

Dec 24, 2010 | Reddy Heater-170,000 BTU Kerosene Deluxe

1 Answer

I have reddy htr 35 was running great,just stopped reset breaker lit right up then went out Pulled cover off fan and spark fine reset it lights right up can see the fuel atomizing flame starts...


Check your fuel lines and most models have a fuel filter in line. A few things come to mind one how old is the fuel? Check the screen in the nozzle assembly by removing nozzle it sits directly behind the nozzle, these corrode and affect fuel flow. While you have this tore down clean the fire-eye with windex and terry cloth rag, it may not be seeing the flame. Check the air filter at the back of the heater as well. These are common problems with these heaters.

Dec 13, 2010 | Reddy Heater-30-55,000 BTU Variable

2 Answers

Vogelzang kerosene heater will not ignite (no spark)


There is an igniter module and then the igniter electrodes (check the air gap) that produces the spark to start the fuel burning, both could be defective.

May 18, 2017 | Reddy Heater-30-55,000 BTU Variable

1 Answer

Lights and runs for 30 seconds then goes out and trips overload switch


Check to see if the pump is leaking some where.Then clean the pump out if there is no leak.Are you burning kerosine?K 1 will give you no problems,but diesel will cause a lot of problems,some reddy heaters can burn both,and some you can not,so look at the warnings.

Oct 17, 2009 | Reddy Heater-30-55,000 BTU Variable

1 Answer

Have a 155000 btu ready heater


It sounds like the unit is tripping the breaker because the breaker is not rated high enough to handle the heaters power usage! If its not that then it may very well be the thermostat needs replaced in unit!
Test at a friends house to see if its your system or the unit!

Dec 18, 2008 | Reddy Heater-30-55,000 BTU Variable

Not finding what you are looking for?
Dayton E50 Heater Logo

Related Topics:

566 people viewed this question

Ask a Question

Usually answered in minutes!

Top Dayton Heating & Cooling Experts

Paul Carew

Level 3 Expert

3250 Answers

Mack Baxter

Level 3 Expert

383 Answers

Dan Webster
Dan Webster

Level 3 Expert

8220 Answers

Are you a Dayton Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...