Question about APC Smart-UPS RT SURT6000RMXLI (APC9672) UPS System

1 Answer

How Icalculate the back periode of ups? - APC Smart-UPS RT SURT6000RMXLI (APC9672) UPS System

Posted by on

1 Answer

  • Level 2:

    An expert who has achieved level 2 by getting 100 points

    MVP:

    An expert that gotĀ 5 achievements.

    Novelist:

    An expert who has written 50 answers of more than 400 characters.

    Governor:

    An expert whose answer gotĀ voted for 20 times.

  • Expert
  • 169 Answers

Look at back of ups, it will have rating plate

eg
230V 3000VA
pf= .7 2100WATTS
72V DC

in this case we have a 230Volt 3kVA ups at .7power factor giving a total of 2100watts of power.

batt is 72Volts DC

ups on bench, batt at full charge with lamp load, usually I connect 75% load eg 1575 Watts, then fail supply and time batts to batt alarm point.
recharge and test again.

can be done with any size ups, other way is to put in data into makers web site and they should give approx batt times for different loads.




Posted on Sep 15, 2009

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

My ups periodically cuts out and comes back as if a reset button is being pressed. The replace battery light is not on but I'm wondering if that's the problem or if the unit is just dying.


could be a battery or it could be a problem with the power supply not being consistent voltage
units seldom die but the internal battery is susceptible to failure over a period of time

Oct 05, 2015 | APC BX 1500 Back-UPS XS 1500 (APNBX1500)...

1 Answer

Freezer stops freezing I unplug it then plug it back in and it starts to run


When you unplug it do you leave it unplugged for a period of time or just real quick? If you leave it unplugged for a long enough period of time it will defrost and then begin to run again for some time before it freezes up again and stop. Not really sure of what your saying when you say stops freezing and then starts to run when you plug it back in.

Jul 29, 2015 | Refrigerators

1 Answer

My xbox360 live is not work


Xbox Live was offline for a number of hours over a number of days in this period. Connectivity was intermittent during this time period. Xbox Live posted a number of warning to the console and online during this period. Xbox Live is back up and running now.

Nov 14, 2014 | Microsoft Xbox 360 Console

1 Answer

Gateway DX4822-01 desktop computer crashes but powers back up after a cool down period. I thought it was a mother board issue and replace the mother board but the same thing is occuring with the new


It is most likely the cpu fan, check to see if you have enough thermal paste on cpu, if not apply a little more and see if that resolve the issue.

Mar 26, 2012 | Gateway Computers & Internet

1 Answer

"Card Locked" message comes up periodically and


Switch of the camera and eject the memory card. carefully take a look @ d side of the memory, u'll find a botton with an indication of Lock and Unlock. Move the botton to the Unlock indication.return the memory card back into the camera carefully and dats all.

Oct 10, 2011 | Polaroid i633 Digital Camera

1 Answer

With gas line removed fuel pump quits running after 5-10sec


That is a built in safety. If you're fuel line were to rupture, you wouldn't want the fuel pump to empty your tank. The pump runs for several seconds until pressure is built up or the time-out period is reached, whichever comes first. If you clamp the end of the fuel line, the pump should run for a very short period to indicate the pressure sensor is working. When the clamp is released, the pump should start back up and run for several seconds until the time out period is reached.

Jun 06, 2011 | 1996 Yamaha XV 535 Virago DX

1 Answer

I signed up 3 mo ago now went back on line cant


3 month is long periods may sites delete ur account for such a long period inactivation.but if ur account still exists just click on link like forgot password or lost password.answer their questions and u will get ur password

Feb 27, 2010 | Computers & Internet

1 Answer

1992 chevy suburban 7.4 454 THM 700 tranny problems!


Try and adjust the down shift cable..Sounds like either it is broke or out of adjustment..

Apr 05, 2009 | 1992 Chevrolet Suburban

Not finding what you are looking for?
APC Smart-UPS RT SURT6000RMXLI (APC9672) UPS System Logo

Related Topics:

70 people viewed this question

Ask a Question

Usually answered in minutes!

Top APC Computers & Internet Experts

Shawn DuRee

Level 3 Expert

355 Answers

Cindy Wells

Level 3 Expert

5096 Answers

Electro Med Services...
Electro Med Services...

Level 3 Expert

6694 Answers

Are you an APC Computer and Internet Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...