SOURCE: Hello have a inverter LG Airconditioner and it
Error Code: C6 Problem: Inverter compressor run current high
SOLUTIONS:
- check [resistance of] compressor windings all equal 1 to 4 ohms
- check [resistance] to earth 50 Mohm minimum
- check run current
I'd also check the motor capacitor(s)
Probably best to explain/print out and give to authorised serviceman
Mat
SOURCE: LG Inverter Air Conditioner showing
CH-02 Indoor Pipe Sensor or Outdoor Sensor Assy fault, Open or Short. Disconnect from PCB and measure resistance. Air sensor = 10 kOhm at 25C, Pipe sensor = 5
kOhm at 25C. If not replace sensor
SOURCE: Our LG Art cool Airconditioner
Inverter compressor run current high. Check compressor windings all equal 1 to 4 OhmsCheck to earth 50 MOhm minimum, check run current. If high, winding is weak. Solution: Replace compressor.