Question about Heating & Cooling

1 Answer

Intertherm furnace circulating air doesnot get very warm furnace butas soon as air getswarm it shuts off . house does n ot get very warm even if furnace runs all day.

Posted by on

  • Anonymous Nov 27, 2007

    FURNACE HAS A 250 DEGREE RESETABLE LIMIT THAT KICKS FLAME OFF. LOCATED INFROUNT ON OUTER VENT PIPE SHOOT. AFTER RESETTING WORKS FOR A SHORT TIME THEN HAVING TO RESET AGAIN. NO RESTRICKTIONS IN EITHER OUTER OR MAIN VENT PIPE.

×

Ad

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    MVP:

    An expert that gotĀ 5 achievements.

    Governor:

    An expert whose answer gotĀ voted for 20 times.

    Hot-Shot:

    An expert who has answered 20 questions.

  • Contributor
  • 49 Answers

That is a stack limit switch. You are not venting properly. Is your unit power ventilated or gravity fed?

Posted on Nov 28, 2007

Ad

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi there,
Save hours of searching online or wasting money on unnecessary repairs by talking to a 6YA Expert who can help you resolve this issue over the phone in a minute or two.

Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.

Here's a link to this great service

Good luck!

Posted on Jan 02, 2017

Ad

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

I HAVE A MODEL UFG-101AG-4 SERIAL # 800H2 INTERTHERM FORCED AIR FURNACE FOR MOBILE HOME OR TRAVEL TRAILER THAT I DONT KNOW WHATS WRONG WITH IT?


OK. Let me answer you, even if honestly I don't have any idea about an INTERTHERM FORCED AIR FURNACE. To get any answer, to a problem, you should describe your problem. Just telling that you don't know what's wrong with it is simply no enough information, even for a star expert in your INTERTHERM FORCED AIR FURNACE.

Jun 25, 2015 | Intertherm Heating & Cooling

1 Answer

I have a 1987 Intertherm FEH-015HA electric furnace. The issue I am having is that my blower will not shut of unless I pull the disconnect. My thermostat will operate the heating elements like normal,


You most likely have a bad fan limit / cycling switch. If you kill the power to the furnace see if you can trace the wires from the motor to where the connect to the switch. It looks like a round button with tabs sticking out of it for the wires to connect. Mark down where the wires were connected and take it to a HVAC business or furnace supply house. Be sure to have the model off the furnace with you so you can get the correct parts.

Nov 25, 2014 | Intertherm Heating & Cooling

1 Answer

Electric furnace will not shut off


Let me know the model number

Nov 18, 2014 | Heating & Cooling

1 Answer

Intertherm furnace parts


if its electric heat one of the sequencers or elements out

Jan 04, 2014 | Intertherm Heating & Cooling

1 Answer

Intertherm Furnace keeps shutting off as soon as it comes on. Model # G5RK072C-12


if its a fossil fuel unit meaning nat gas or propane and it lights then goes out in a few seconds try cleaning the flame sensor take out sensor then rub it gently with steel wool then replace should solve problem

Jan 24, 2011 | Intertherm Heating & Cooling

1 Answer

When I turn on my furance or ac the blower is always on even though the fan is set to auto. When it is on heat it never gives off any hot air, so it never warms up the house. I had someone look at it and...


If this is a mobile home furnace they usually have a two stage gas valve. Generally they just have a delay in opening fully and are convertable from L.P to natural gas or vice versa. It is a possibilty that the gas valve is bad. If so it will have to be replaced. First I would have someone check your thermostat to see if that is what is causeing the blower to run . does the burner ever light? I wouldsuggest that you hire a service tech. who is knowledgable on intertherm furnaces. I don't recommend anyone who is not trained to change gas valves,because of safty concerns. I hope this helps you some. Thanks

Nov 12, 2010 | Intertherm Heating & Cooling

1 Answer

The Intertherm AC Model B3BV-030K-A is blowing warm air


If you don’t see any frost on the suction line or big line on the furnace
(that goes from the furnace to the outdoor unit) and the filter and coil are clean then you are probably low on refrigerant.

Apr 14, 2009 | Heating & Cooling

1 Answer

Blowing luke warm sometimes and hot others


you have a bad breaker and need to replace it. when you put the load all on one you are taking a chance on having to replace both of them. Thae are not made ot be shut off and on to manty times.

Jan 21, 2009 | Heating & Cooling

2 Answers

Intertherm gas furnace model number m6bb070abfc01


Check for a open limit switch caused by a dirty filter or poor air flow

Dec 24, 2007 | Intertherm P3RA-048K Air Conditioner

Not finding what you are looking for?
Heating & Cooling Logo

Related Topics:

149 people viewed this question

Ask a Question

Usually answered in minutes!

Top Heating & Cooling Experts

Paul Carew

Level 3 Expert

3280 Answers

Dan Webster
Dan Webster

Level 3 Expert

8220 Answers

Tim Whalen

Level 3 Expert

3074 Answers

Are you a Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...