The Main reasons that this will happen
1 - A bad run capacitor (silver or metal capacitor)
It’s either shorted, grounded or open.
If it’s shorted a lot of times it will bulge out, (sometimes slightly)
2 - A bad start kit ( plastic capacitor and Relay connected to it )
The capacitor is either shorted or open
The relay either has an open coil between terminals #1 and #5
Or the relay is stuck.
Any time you change the capacitor or relay you should change
the other, especially if they are over a year old.
3 - A loose, burnt or disconnected wire
4 - Wired wrong
5 Compressor is open (windings burnt open)
6 Low on charge not getting enough cooling back to compressor, (Feel top of compressor to see if it’s hot it shouldn‘t be)
7 Some compressors have a black plastic overload under the compressor cap which could be bad.