THE THERE WAS NO POWER AND THE UPS WENT OFF,NOW BATTERY BREAKERS tripped and cannot come on,also there is configuration error alarm .the unit is not coming on

Posted by on

Ad

1 Answer

  • Level 2:

    An expert who has achieved level 2 by getting 100 points

    All-Star:

    An expert that got 10 achievements.

    MVP:

    An expert that got 5 achievements.

    Mentor:

    An expert who has written 3 tips or uploaded 2 video tips.

  • Expert
  • 175 Answers

You blew the logic board. That is the configuration error alarm. Batteries are tripping because batteries are bad.

Posted on Jul 29, 2015

Ad

5 Suggested Answers

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
A 6ya expert can help you resolve that issue over the phone in a minute or two.
Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
The service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
Good luck!

Posted on Jan 02, 2017

Ad
  • 37 Answers

SOURCE: Opti-UPS 1400ES UPS unit - Beeping 14 Times, stops, Beeps Again.

you can try this asia systems technologies look for our sale person william +65 65478990 william@asiasystemstech.com i suspected that now that u UPS is have hardware issue.. to determine if the unit is really the problem it hav to be do a further diagnos..

Posted on Mar 24, 2009

uk8ahw
  • 3 Answers

SOURCE: Unwaranted UT3K UPS check battery warning

Hi!
1) By the way, batteries are really new (or "China new")? ;)
If they really new then maybe not start-formed. In this case after little time they will get steady (end of problem). If they are "China new" - it worse, their real capacity usually less then 75% from declared.
2) Try to check batteries connectors, wires and their eyelets. If there is weak contact - charging will be wrong (low current)...
3) Check small orange (voltage sence) connector...
4) Look, what happened with P-62, P-63, P-74 ang P-75 settings? maybe there something is wrong...

Maybe, it will be helpfull?
P.S. Please, excuse my weak english.

Posted on Apr 14, 2009

  • 55 Answers

SOURCE: UPS does not supply power to equipment after power trip

Some of the less expensive UPS devices have two sets of plugs.  One set provides backup power and the other set only provides surge protection.  You need to ensure that the devices for which you want backup power are plugged into the correct outlets on the UPS.

Posted on Apr 26, 2009

  • 15 Answers

SOURCE: "On Battery" Alarm Sounds when Power Available.

if this comes sometimes and goes, this means that the power to ups is sometimes deviating from the specific ups input range, hence the ups is rejecting it. mesure the input voltagesand frequency with a multimeter and check whether they match the specified ones in the ups manual. aslo with some ups there are switches that you use to set the input voltages or number of phases in the ups input. check the manual to see whetther your ups has such.

Posted on Oct 25, 2009

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

2 Answers

How to reset configuration error of the UPS 9390?


This error can only be cleared by the Eaton technician with their laptops. If this is a new unit it HAS to be factory started or your warranty will be void.

Apr 02, 2015 | Powerware 9390 UPS System

1 Answer

Liebert gxt2-10000t230 low batt,bypass light flashing,no output,shutdown after a minute


Test outlet power by switching the unit to manual bypass and breakers off.
If power is supplied OK and the filter board repaired OK then restart the unit starting with the breakers supply to unit,battery confirm the display is on and static bypass led also on then switch back the bypass knob to normal and press the on button to switch the unit to normal.
Give the batteries time to charge 12hours then you can test the unit on backup mode.

Nov 25, 2014 | Liebert (GXT2-10000T230) (GXT2-10000T230)...

1 Answer

Belkin battery backup bu3dc000-12v alarms


Hi Mike,

Electronic circuit issue,

you have to repair unit or replace the circuit bord.

regards,
nuwan.

Jan 11, 2014 | Power-Sonic Belkin 84Whr BU3DC000-12V UPS...

2 Answers

Error light in my apc smart ups sc 1500va ups


1. Four beeps every 30seconds (On Battery LED will be illuminated)
This alarm indicates that the Battery PowerSupplied outlets are now supplying battery power as opposed to power from theutility. If the UPS determines that the input utility power is unsafe for yourcomputer equipment, the UPS will switch to battery power.
Note: Ifthe power disturbance is brief, you may only hear one or two beeps.

2. Continuous Beeping (On Battery LED will beilluminated)
This alarm indicates that a Low Batterycondition has been reached and that the UPS will soon shutdown. Once the UPStransfers to On Battery operation, it can only stay on battery for a limitedamount of time. The UPS will sound this alarm about two minutes before thebatteries are totally exhausted. Once exhausted, the UPS will shutdown and turnoff its output power to your equipment. If you hear this tone you shouldimmediately shutdown your computer to prevent data loss or corruption.

3. Continuous Beeps for 30 seconds (BackUPS OFFICE 250 and 280 ONLY)
This alarm indicates the unit has detected anOverload condition after it has performed a self-test during start-up.

4. Continuous Two-Tone Beep
This alarm indicates a severe Overload wasdetected while the unit was on-battery operation. This tone will continue tosound until the unit shuts down.

5. Continuous Tone (On Battery LED will beflashing)
This alarm indicates that the battery-poweredoutlets are overloaded.

6. Continuous Tone (On Line and On BatteryLEDs flashing) Back UPS OFFICE 350,400, and 500 ONLY
This alarm indicates that an internal UPS faulthas occurred.

Dec 08, 2011 | APC Smart-UPS SC 1500VA UPS System

1 Answer

SO bad, and a bad response... I have 2 UPCs one started beeping for no reason, and will not stop...even when plugged into the wall with the battery disconnected... The other one is still silent. SO the...


These beep error codes may help you.
1. Four beeps every 30 seconds (On Battery LEDwill be illuminated)
This alarm indicates that the Battery Power Suppliedoutlets are now supplying battery power as opposed to power from the utility.If the UPS determines that the input utility power is unsafe for your computerequipment, the UPS will switch to battery power.
Note: Ifthe power disturbance is brief, you may only hear one or two beeps.

2. Continuous Beeping (On Battery LED will beilluminated)
This alarm indicates that a Low Battery condition hasbeen reached and that the UPS will soon shutdown. Once the UPS transfers to OnBattery operation, it can only stay on battery for a limited amount of time.The UPS will sound this alarm about two minutes before the batteries aretotally exhausted. Once exhausted, the UPS will shutdown and turn off itsoutput power to your equipment. If you hear this tone you should immediatelyshutdown your computer to prevent data loss or corruption.

3. Continuous Beeps for 30 seconds (Back UPSOFFICE 250 and 280 ONLY)
This alarm indicates the unit has detected an Overloadcondition after it has performed a self-test during start-up.

4. Continuous Two-Tone Beep
This alarm indicates a severe Overload was detectedwhile the unit was on-battery operation. This tone will continue to sound untilthe unit shuts down.

5. Continuous Tone (On Battery LED will beflashing)
This alarm indicates that the battery-powered outletsare overloaded.

6. Continuous Tone (On Line and On Battery LEDsflashing) Back UPS OFFICE 350, 400, and 500 ONLY
This alarm indicates that an internal UPS fault hasoccurred.

Feb 28, 2011 | APC Back-UPS Pro 650 UPS System

2 Answers

On our 20kVa unit we got a 'battery must be checked" alarm. We replaced the battery but alarm still on unit. How can we get rid of this? We already did the normal reset but alarm still there. Thank...


The internal automatic battery test is picking up some differences between the actual value of the battery to the mathematical calculation used in the software. Normally if you do a battery impedance test you would find that the batteries would be consistent and therefore replacing the batteries may not be the solution. Once you transfer the UPS on BYPASS and then recycle the power you would clear the alarm. However on the next internal automatic battery you would be getting the same alarm again.

At times this may be a software issue or an SNMP problem. Normally to refresh the battery data for the UPS monitoring software we carry out a battery discharge test. Please consult with the supplier if an annually battery discharge test is mandatory for the battery monitoring circuit to work well. Please let me know of the outcome

Feb 04, 2011 | MGE UPS Galaxy 3000 UPS System

1 Answer

Strange noise comes out from the ups after a power cut


The Back-UPS Office unit has five different tones or alarms:

1. Four beeps every 30 seconds (On Battery LED will be illuminated)
This alarm indicates that the Battery Power Supplied outlets are now supplying battery power as opposed to power from the utility. If the UPS determines that the input utility power is unsafe for your computer equipment, the UPS will switch to battery power.
Note: If the power disturbance is brief, you may only hear one or two beeps.

2. Continuous Beeping (On Battery LED will be illuminated)
This alarm indicates that a Low Battery condition has been reached and that the UPS will soon shutdown. Once the UPS transfers to On Battery operation, it can only stay on battery for a limited amount of time. The UPS will sound this alarm about two minutes before the batteries are totally exhausted. Once exhausted, the UPS will shutdown and turn off its output power to your equipment. If you hear this tone you should immediately shutdown your computer to prevent data loss or corruption.

3. Continuous Beeps for 30 seconds (Back UPS OFFICE 250 and 280 ONLY)
This alarm indicates the unit has detected an Overload condition after it has performed a self-test during start-up.

4. Continuous Two-Tone Beep
This alarm indicates a severe Overload was detected while the unit was on-battery operation. This tone will continue to sound until the unit shuts down.

5. Continuous Tone (On Battery LED will be flashing)
This alarm indicates that the battery-powered outlets are overloaded.

6. Continuous Tone (On Line and On Battery LEDs flashing) Back UPS OFFICE 350, 400, and 500 ONLY
This alarm indicates that an internal UPS fault has occurred.

Jan 06, 2010 | APC Back-UPS ES 700 - UPS ( external ) -...

2 Answers

"On Battery" Alarm Sounds when Power Available.


if this comes sometimes and goes, this means that the power to ups is sometimes deviating from the specific ups input range, hence the ups is rejecting it. mesure the input voltagesand frequency with a multimeter and check whether they match the specified ones in the ups manual. aslo with some ups there are switches that you use to set the input voltages or number of phases in the ups input. check the manual to see whetther your ups has such.

Oct 24, 2009 | APC BX800 Back-UPS XS 800 (APNBX800) UPS...

1 Answer

Burnt out


internal failure possibly on power side, lower than 300A fault current so unit could not trip i/p protection and as fault was post ac section, continued to burn internally.
it just broke
no breakers tripped out so it kept drawing current until the fault burnt away.


maybe this is what happened, need to know a lot more info to change hypothisis


Jun 01, 2009 | Vector VEC056D 2500 Watt Power Inverter...

1 Answer

A-12 Alarm wont go away



I have an ut8k UPS I am getting an A-12 alarm. On the cover it means "tap the regulator alarm. I opened up the unit ...

May 28, 2009 | Powerware Best Power Unity/I Single-Phase...

Not finding what you are looking for?
Computers & Internet Logo

Related Topics:

307 people viewed this question

Ask a Question

Usually answered in minutes!

Top Power Computers & Internet Experts

waruna

Level 2 Expert

47 Answers

Pieter Vleeshouwers
Pieter Vleeshouwers

Level 3 Expert

1882 Answers

yadayada
yadayada

Level 3 Expert

78237 Answers

Are you a Power Computer and Internet Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...