It could be going out on a high head pressure safety
Agree, wash the coil if it still keeps going off its probably overcharged, or too small of liquid line going inside must be 3/8" minimum if it's a new 410a which being a 13 seer guessing it is.
Sorry scratch the liquid line just looked again at description. You need a new coil inside almost grantee those dry ship 13 seer are a waste of money I did one myself it failed within a week I do not offer them and never well again.
They claim to save money by not changing the indoor coil but just because it's the same refrigerant does not change the fact you need a 13 seer rated coil. They should stop selling these dry shipped heck $75 -$90a pound r-22 vs $18-$25 a pound 410a it makes no sense anyways.
×
Check the pipes right next to air unit outside is the large one nice very cold an the small pipe warm or very hot
is the exhaust air blowing up really hard can't hold hand over its so fast and hot/warm .