Anonymous Posted on Jul 04, 2014

House a/c compressor runs for a while then shuts off

2 Answers

ardvark02

Level 1:

An expert who has achieved level 1.

Hot-Shot:

An expert who has answered 20 questions.

Corporal:

An expert that hasĀ over 10 points.

Problem Solver:

An expert who has answered 5 questions.

  • Contributor 43 Answers
  • Posted on Aug 02, 2014
ardvark02
Contributor
Level 1:

An expert who has achieved level 1.

Hot-Shot:

An expert who has answered 20 questions.

Corporal:

An expert that hasĀ over 10 points.

Problem Solver:

An expert who has answered 5 questions.

Joined: Jun 21, 2008
Answers
43
Questions
1
Helped
7547
Points
51

It could be going out on a high head pressure safety

  • 1 more comment 
  • Chris Gorman
    Chris Gorman Aug 14, 2014

    Agree, wash the coil if it still keeps going off its probably overcharged, or too small of liquid line going inside must be 3/8" minimum if it's a new 410a which being a 13 seer guessing it is.

  • Chris Gorman
    Chris Gorman Aug 14, 2014

    Sorry scratch the liquid line just looked again at description. You need a new coil inside almost grantee those dry ship 13 seer are a waste of money I did one myself it failed within a week I do not offer them and never well again.

  • Chris Gorman
    Chris Gorman Aug 14, 2014

    They claim to save money by not changing the indoor coil but just because it's the same refrigerant does not change the fact you need a 13 seer rated coil. They should stop selling these dry shipped heck $75 -$90a pound r-22 vs $18-$25 a pound 410a it makes no sense anyways.

×

Karl Whisenand

Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that gotĀ 10 achievements.

MVP:

An expert that gotĀ 5 achievements.

Genius:

An expert who has answered 1,000 questions.

  • Master 1,554 Answers
  • Posted on Aug 17, 2014
Karl Whisenand
Master
Level 3:

An expert who has achieved level 3 by getting 1000 points

All-Star:

An expert that gotĀ 10 achievements.

MVP:

An expert that gotĀ 5 achievements.

Genius:

An expert who has answered 1,000 questions.

Joined: Jan 21, 2008
Answers
1554
Questions
1
Helped
752907
Points
4266

Check the pipes right next to air unit outside is the large one nice very cold an the small pipe warm or very hot
is the exhaust air blowing up really hard can't hold hand over its so fast and hot/warm .

Ad

Add Your Answer

×

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

0helpful
1answer

A/C compressor shutting on and off at different intervals

When cu shuts down does the contactor release?When compressor shuts off are you still getting 24 all the way to contactor?? If system shuts down with contactor pulled in it's a high voltage issue. If contactor lets go then you know it's a low voltage issue. Possible short, check tstat wire for rodent damage. Tighten high voltage wires in disconnect, be safe!!
1helpful
1answer

Craftsman model #921166390 motor

The motor does not take oil on that unit. The compressor housing does though. If you cant get it to start after it ran dry, the cylinder is most likely seized to the piston.
0helpful
1answer
0helpful
1answer

The air continues to run after setting thermostat

mcdevito75 here, The FAN will continue to run this is normal but the compressor should shut off at intervals, you can usually hear the compressor going on / off. If your sure the compressor continualy runs, contact your local a A/C repair shop, they come to the house.
2helpful
1answer

Clunk noise when compressor shuts off

Good day,
Compressor has an internal problem. Usually caused by a broken centering spring inside the compressor housing.
Only solution is replacing the compressor.
The good news is they can run for along time that way.
3helpful
1answer

Humidifier compressor does not stay on more than 1-2 minutes

Sounds like bad relay on compressor or bad compressor. There is only so far you can go yourself without knowledge in electrical and AC units. Suggest you call a service tech or if you can take it to service cemter near you. Russ
0helpful
2answers

When compressor on the blower keeps trying to shut down.

You may have a bad capacitor. But you may nee a service tech to check it out. There is only so far you can go without knowledge of Air Conditioning. Ask for free estimate and you will know upfront what the cost is . RUS
4helpful
1answer

Dehumidifer runs for about 45sec to 1minute and then shuts off. wqhat would be making this happen

If it does that consistently, then it's likely that the compressor is overheating and shutting down. (It has a thermal overload circuit to prevent a potential fire). Another cause could be a malfunction of the control circuit board which runs all functions of the unit. To check for possible compressor problem, unplug the unit, remove the housing to expose the compressor, plug it back in and power it up. When it shuts down, feel the compressor. It should be warm to the touch, but definitely not so hot that it singes your fingers.

If you find that the compressor is just normal warm, then the control circuit board is shot and needs to be replaced. Check with the merchant or manufacturer for availability & cost. If prohibitive, you're better off simply replacing that unit with a new one.
23helpful
1answer

4wd wont work on 1999 chevy tracker but front drive shaft is turning?

The locking hub control system is not engaging properly. On the 99 Tracker this is a compressed air system that consists of an air pump (compressor), electrical wiring to power and control the air pump, and air hoses that lead to an actuator inside the front differential housing. If there is a leak in the system the PCM will run the air pump for 10 seconds and then shut off, and your propeller shaft can turn all day long, but the front axles will remain free floating. Turn on your key, not your engine, and engage four wheel high. Go listen near the passenger front bumper for the air compressor. If you hear it, then the compressor control and the compressor itself are likely fine. If it shuts off after 10 secs or so, and your 4WD light isn’t on, the PCM timed out the compressor out and shut the compressor off to protect it. You will have to find the leak and fix it. If you are lucky, it’s the air line leading to the front differential; and not the air line inside the differential housing, or the air bladder in the locking actuator, which also resides inside the font diff. If the compressor shuts off and the 4WD light is on (this means the PCM did not shut the air compressor off due to timeout, so the pressure switch read 5-7 psi and the pump shut itself off), you likely don’t have a leak, and something mechanical has the actuator hung up inside the front differential. Lastly if you don't hear the compressor run at all, you either have a faulty compressor, or some sort of wiring problem in that circuit.....it could be as simple as a blown fuse. Good luck.
Not finding what you are looking for?

113 views

Ask a Question

Usually answered in minutes!

Top Ruud Heating & Cooling Experts

Brad Brown

Level 3 Expert

19187 Answers

Ronny Bennett Sr.
Ronny Bennett Sr.

Level 3 Expert

6988 Answers

john h

Level 3 Expert

29494 Answers

Are you a Ruud Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...