You probably have T104 timer.
Clock rotates so power to timer motor is good. This means 240Volt breaker is good.
Use override lever and see if Load (light, fan, motor) turns on and off. If override does not turn Load on-off, then bypass timer and see if load works. Move wires from terminal 2 to terminal 1, and terminals 4 to terminal 3.
Did you order correct trippers?
Copy following links for Intermatic troubleshooting and Intermatic parts list.
http://waterheatertimer.org/How-to-troubleshoot-Intermatic-timers.html
http://waterheatertimer.org/Intermatic-trippers-and-parts.html#T100