1992 NORDYNE/INTERTHERM FEHA-015HA-01 DOES THIS UNIT HAVE FUSES

BLOWER WON'TKICK ON MOTOR IS GOOD NEW CAPACITOR AND THERMASTAT DOES THIS UNIT HAVE FUSES?

Posted by Anonymous on

Ad

1 Answer

  • Level 2:

    An expert who has achieved level 2 by getting 100 points

    MVP:

    An expert that gotĀ 5 achievements.

    Sergeant:

    An expert that hasĀ over 500 points.

    Champion:

    An expert who has answered 200 questions.

  • Expert
  • 234 Answers

It should have a 3 or 5 amp fuse on the circuit board.

Posted on Nov 26, 2014

Ad

3 Suggested Answers

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of.(from cars to computers, handyman, and even drones)
click here to download the app (for users in the US for now) and get all the help you need.
Goodluck!

Posted on Jan 02, 2017

Ad
  • 25 Answers

SOURCE: WONT COOL OUTSIDE UNIT DOES NOT COME ON FAN BLOWS INSIDE

if the fan outside is turning on and inside fan is blowing too, then you have a compressor problem. could be a capacitor gone bad (or needing a hard start kit) to the entire compressor failure

Posted on Oct 09, 2009

  • 415 Answers

SOURCE: Thermostat wiring diagram for Intertherm FEHA-015HA-01

Installation Manual

Posted on May 19, 2010

Testimonial: "EXCELLENT EXACTLY WHAT I NEEDED!!!! THANKS!!!!"

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

Why is my Intertherm nordyne ac unit fan not coming on?


It could be a bad wire or broken,burned etc. Or the capacitor is bad. The motor may have seized up.

Apr 29, 2014 | Intertherm Heating & Cooling

1 Answer

I have a intertherm e2eb-012ha. I need to know what size run cap to use. . The plastic coating has been melted so I can not see the run cap info.


It appears you may already have located your problem, the capacitors are very coming to burn out, if a motor will run after you spin by hand, mmore times than not the capacitor is the problem. The name tag on the equipment itself sometimes has the capacitor size and the motor nameplate usually does as well. you can call Nordyne support at 18004224328 and with your Intertherm Model number they can give you the correct capacitor size, which you can purchase at any HVAC supply house. If I had to guess, I would say you need a 5 mfd capacitor based on the blower size. but call them and verify. Also, most all supply houses that sell that capacitor can run the Intertherm numbers and see the correct size as well.

Jan 06, 2013 | Heating & Cooling

1 Answer

HEATER MODEL FEHA-015HA-01 SN FEH9302-03330 BLOWER WON'T KICK ON IN HEATER. MOST OF THE TIME, TAPPING ON RACEWAY PANEL OR RELAY BOX COVER WILL MAKE IT COME ON. DO YOU KNOW WHAT THE PROBLEM COULD BE?


Sounds like a bad fan relay or sequencer. From your model number it looks like a 15 kw heat. Some unit the first stage heat brings on the fan. So I would replace sequencer and that should solve your problem. Easy to change. Just replace wire per wire. Rus

Dec 07, 2009 | Refrigerators

1 Answer

WONT COOL OUTSIDE UNIT DOES NOT COME ON FAN BLOWS INSIDE


if the fan outside is turning on and inside fan is blowing too, then you have a compressor problem. could be a capacitor gone bad (or needing a hard start kit) to the entire compressor failure

May 03, 2009 | Intertherm P3RA-036K Air Conditioner

3 Answers

Anyone have a wireing diagram for a nordyne E1EH-015HA


Intertherm does not offer a wiring diagram for the E1 series anymore. So I have included a link to the E2 series. They are very similar and you may find this service manual helpful for whatever problem you may be having.

http://www.nordyne.com/literature/359a.pdf

Apr 11, 2009 | Heating & Cooling

2 Answers

Need a schematic for nordyne intertherm model e1eb-015ha


Nordyne no longer has the E1 model in there literature not even in their archieved documents but I have included a link to for the E2 model which will be very similar to yours. These units are very simple and all only vary slightly. It should give you enough info to get you through what you want to know.

http://www.nordyne.com/literature/7103180.pdf

Apr 04, 2009 | Heating & Cooling

1 Answer

No heat fan running


This is a 10 Seer electric heat package unit. There are few possibilities. Does the blower come on when you put the t-stat on Fan on? If it does, then it is probably the blower time delay relay which is nordyne part# 622181. If the blower doesn't come on at all, check that the blower is getting power and if it is, then the blower motor is bad but could possibly be the capacitor as well. Both should be checked.

Mar 31, 2009 | Intertherm P3RA-036K Air Conditioner

4 Answers

WIRING


why did the wiring burn?Id have the heat exchanger inspected before rewiring.better to be safe.

Sep 17, 2008 | Intertherm P3RA-048K Air Conditioner

Not finding what you are looking for?
Heating & Cooling Logo

Related Topics:

112 people viewed this question

Ask a Question

Usually answered in minutes!

Top Intertherm Heating & Cooling Experts

Donni Steen

Level 3 Expert

659 Answers

Dennis Boxerman

Level 3 Expert

1151 Answers

Dan Webster
Dan Webster

Level 3 Expert

8220 Answers

Are you an Intertherm Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...