My Coleman Powermate Pulse 1750 generator shuts down

As stated, my generator shuts down when I try to run my skilsaw. My saw draws 10 amps. Generator is rated for 15. Do I have an internal problem with the generator? Shouldn't this unit run a drill or skilsaw without a problem?

Posted by on

Ad

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    Mayor:

    An expert whose answer got voted for 2 times.

  • Contributor
  • 1 Answer

Your generator should run a power tool rated at 10 amps. The 15 amps you mentioned for the PM1750 is for the DC rating. The AC rating is 11.6 amps.

Posted on Jul 03, 2009

Testimonial: "Thanks for the update. Checked out everything again and tried different tools. You were right on the money. Thanks"

Ad

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
A 6ya expert can help you resolve that issue over the phone in a minute or two.
Best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
The service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
Good luck!

Posted on Jan 02, 2017

Ad

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

1 Answer

I cannot locate the owners manual for my Coleman PowerMate 6250 generator 10 hp? Any place I can find this online quickly thank you


Most PowerMate manuals are available here: http://www.powermate.com/productmanuals.php?cat_id=3 . However, describing it as the PowerMate 6250 10 HP generator is insufficient to find the correct manual. The Coleman PowerMate line has several models with 10 HP engines and a 6250 Starting Watt (5000 W running) capacity.

These include the Powermate PM0435005; the direct link for this manual is http://www.powermate.com/pdfs/2011/12/29/pm0435005.02.pdf .

Please add a comment with the actual model number of your generator if you need further assistance with finding the correct manual for your generator.

I hope this helps.

Cindy Wells

Sep 05, 2017 | Coleman Electrical Supplies

1 Answer

I HAVE A POWERMATE 5000 THAT SHUTS DOWN UNDER LARGE LOAD . I THINK I NEED AN IDLE CONTROL MODULE.THERE IS A 2 WIRE MODULE IN THE START CKT. #21009XA IS THIS IT AND WHERE DO I GET ONE .


Idle control comes into play when there is no power draw forcing the engine to idle with an electro magent. If you feel that the electro magnet is interfering with governor, temp remove the wire to the solenoid. Usually the idle control will not effect how the engine /gen output power. An overloaded condition will cause the engine the go the full throttle as the internal governor of the engine will try to maintain 3600 rpm. Overloaded condition will greatly shorten the life of the generator/engine. Try to use only about 80 % of rated power. Large motors can draw three times running amps. A compressor using 12 to 18 amps to run can draw over 40 amps to start.
If your generator could handle the load in the past, check the engine for loss of power, or the generator for faulty voltage regulator or capacitors out of range. Easy to check. Connect digital volt meter to plug /load and look at volt reading while running with no load and loaded. Voltage should stay between 110 to 120 under load and with no load (unless goes into idle mode). Good luck

Sep 06, 2011 | Coleman Powermate Powermate 5000W...

1 Answer

Powermate plus 1750 portable generator. Has fresh gas, will just runs a couple of seconds on starter fluid and just stops.


It could be a number of thinks. plugged fuel line, carburetor, but dont use to much starter fluid this can burn a hole in the top of your piston. check to see if its getting any spark.

Aug 14, 2011 | Coleman Powermate Premium Plus 6250W...

1 Answer

I bought a used coleman powermate 5000 generator, I replaced the spark plug and fuel filter, it finally started up,it would only run in the "choke" position it ran about 10 minutes and then shut down, I...


What brand of engine & horsepower is it?Also about how long was it stored or last time it was run? The reason I ask is if it was stored with gas in it & a fuel stabilizer wasn't added to it,your primary jet is plugged in the carburetor(reason it will only run while choked).

Jan 07, 2010 | Coleman Powermate Powermate 5000W...

1 Answer

I have a coleman powermate 6875 engine runs fine and it all works till it gets hot then the engine still runs but not charging.


The unit should have a pop out fuse or set of fuses.
If you are drawing too much currant from the unit, it will shut down. If you plug in a simple 100Watt light and test the unit and see if it stops generating currant.
Max is only 5500.
You may also have shutoff thermo sensiors, if the caseing of the generator runs too hot or low on oil, it will shut unit down.

Keep in mind, if you have a shut off valve, turn the shut off valve, closing the fuel supply while running.
This will remove all gas from the bowl and not spoil after setting for long periods of time.
Same with oil, it will do damage to the engine if it just sets for long periods.

Sep 23, 2009 | Coleman Powermate Premium Plus 6250W...

2 Answers

I have a Coleman Powermate Pulse 1750 generator. The engine runs fine but lately I've noticed I'm only getting approx. 105 volts. Any suggestions.


Engine speed is low, does your meter read frequency? Set for 60 Hz @ speed. I doubt there is a voltage regulator adjustment. This may help

Jun 25, 2009 | Coleman Powermate Premium Plus 6250W...

2 Answers

Need manual for coleman powermate 1850 generator


google it! use the specific search terms, Coleman power pulse 1850 - it worked for me!

Jun 05, 2009 | Coleman 10' X 10' Sundome Tent 9160K101

Not finding what you are looking for?
Coleman 10' X 10' Sundome Tent 9160K101 Logo

1,773 people viewed this question

Ask a Question

Usually answered in minutes!

Top Coleman Sport & Outdoor - Others Experts

David Payne
David Payne

Level 3 Expert

14162 Answers

Vernon Taylor

Level 3 Expert

4403 Answers

Thomas Perkins
Thomas Perkins

Level 3 Expert

14405 Answers

Are you a Coleman Sport and Outdoor - Other Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...