Question about Goodman GMS90703BXA Heater

1 Answer

Cool turned down to 65 and it is still 81 in the house

Goodman heat pump one year old. It sounds like the fan is running but maybe not the compressor. It is blowing cool air but not cold.

Posted by on

  • Jim Goldsmith
    Jim Goldsmith May 11, 2010

    while it is running place your hand on the compressor and feel for vibration

  • steve
    steve May 11, 2010

    Do you have a amp meter?

×

1 Answer

  • Level 1:

    An expert who has achieved level 1.

    Corporal:

    An expert that hasĀ over 10 points.

    Problem Solver:

    An expert who has answered 5 questions.

  • Contributor
  • 6 Answers

To see if the compressor is running feel your line set the liquid line
(small line) should feel like there is fluid flowing though it, you can also disconnect the o/d fan briefly if you want to be certain the compressor is running, it best however to get a meter and amp clap to do a proper diagnosis, you are limited to your tools as well as your knowledge, call an NATE certified professional.

Posted on May 27, 2009

1 Suggested Answer

6ya6ya
  • 2 Answers

SOURCE: I have freestanding Series 8 dishwasher. Lately during the filling cycle water hammer is occurring. How can this be resolved

Hi,
a 6ya expert can help you resolve that issue over the phone in a minute or two.
best thing about this new service is that you are never placed on hold and get to talk to real repairmen in the US.
the service is completely free and covers almost anything you can think of (from cars to computers, handyman, and even drones).
click here to download the app (for users in the US for now) and get all the help you need.
goodluck!

Posted on Jan 02, 2017

Add Your Answer

Uploading: 0%

my-video-file.mp4

Complete. Click "Add" to insert your video. Add

×

Loading...
Loading...

Related Questions:

2 Answers

Goodman outdoor a/c unit top fan stopped working while the family was away from home and now the compressor will not turn on. Only thing happening when a/c turned on inside is the indoor unit kicks on and...


the fan would need to be changed also it may have over heated the pump. if it has been left for a long time in this way it could of done more damage. you could be luck and that the fan might be telling the unit control its not moving so it will not turn on. but to find this out you will need to replace the fan if the fan has 3 or more wire it would have this feature.

Jun 27, 2017 | Heating & Cooling

1 Answer

My Amana heat pump model PTH153B50AJ does not cool properly. The compressor comes on and the fan works.


This sounds like a freon problem your system probably has a leak in the system somewhere. Amana has tons of problems with there equipment. They make there coils paper thin and they split especially on a heatpump. Amana used to be a good brand and then got bought out by goodman manufacturing and have turned there product into ****. How old is this unit?

Jun 14, 2011 | Amana PTH153B50AJ Heat Pump Air...

1 Answer

I have two outside ac one for floor and other for upstairs and i button on heater auto and ac outside fan is running is that normal or not? and live on this new house for two years and cant find someone...


No the fan out side is for a condensing unit and compressor. The compressor should not run with the heat. I am almost positive that if this is not a heat pump that the compressor unit should not be running.

Dec 20, 2010 | Goodman GMS90703BXA Heater

1 Answer

We gave a Goodmn Hertz 60 Phase I heat pump - installed this summer....worked great for cooling..now that temps are dropping we are needing heat. When we turn it on it comes on but never heats. Think it...


If you changed the unit but didn't change the thermostat it is possible that the thermostat that you have will not work with that unit. I see that the unit you installed is a heat pump, you may have a straight cool T-Stat. If you put the T-Stat in the "Auto" "Heat" mode the outdoor fan and the compressor should be workng as well as the blower fan. If it turns out that the outdoor fan and compressor are not running you will want to buy a Thernostat that is compatable with heatpumps should be 2 heat/ 1 cool

Nov 05, 2010 | Goodman PHKJ048-1 Air Conditioner

1 Answer

Goodman heat pump stopped cooling


yes, but I would try a "hard-start" kit before replacing the compressor itself

Jul 10, 2010 | Goodman CPLE24-1 Air Conditioner

1 Answer

3 year-old Goodman compressor/heat pump terribly loud @ start


Without being there to see it and have only your description in front of me, it sounds like the fan blade could be out of balance.......but it sounds more like a loose fan blade hub. Most Goodman units offer a minimum 5 year parts warranty. The Labor warranty is questionable, but the installing contractor or the Goodman Distributor should be able to give you that information. Of course this would cover manufacturer problems and not physical damage. As far as a history of this problem with Goodman..........I've seen it with every brand. If there is a problem getting it under warranty, you might be able to purchase the blade yourself. Before replacing the fan blade, I recommend disconnecting the motor wires from the contactor, tape off the ends and remember exactly where they were attached.....then start the unit to see if the noise is still evident, if so, it's probably your compressor. I recommend a certified repairman....not the one that quoted you $800.00. If you hear only the compressor start up and not the loud noise you are discribing, then try replacing the blade first.

I hope you find this information to be very helpful to you. :-)

Mar 16, 2010 | Goodman CKL60AR60 Air Conditioner

2 Answers

Goodman a/c blower runs on auto and humidity problems


Is the air cold inside? You are talking about the fan inside? Have system check for freon but more than likely, it sounds like a t'stat problem. And it's not normal for the fan to run constantly.

Jul 05, 2009 | Goodman CLQ36AR49 Air Conditioner

6 Answers

Condenser fan running backwards on heat pump


I am having the same problem, sometimes it runs in the wrong direction, blowing the air down. Sometimes something gets tripped and I need to turn the thermostat to off and wait a bit then restart it. If I am lucky it will run int the correct direction and also will warm the house. Sometimes it send nothing but cold air to the house's forced air.

Jun 13, 2009 | Goodman CKL24AR24 Air Conditioner

1 Answer

Blower in house runs, but compressor outside does not


Sounds like control voltage problem. Tsat mat be bad. It is hard to say without looking. Next time this happens. Have someone stands out side by the unit to see if the contactor is pulling in. When you turn the Tstat off and wait and turn it on you may be manually make the contact in the Tstat. If the fan and compressor are not running when you call for cool, Most of the time it is the control voltage. Let me know if the outside fan runs and the compressor does not. Rusty

Jun 06, 2009 | Goodman CKL42AR42 Air Conditioner

1 Answer

Heat pump not running


check your house circuit breakers first that should be labeled heatpump or outdoor unit
make sure it is on and or not tripped
then if you have a box outside near the outdoor unit open it up and see if there is a breaker or maybe fuses that could be blown

May 26, 2009 | Goodman CPLE24-1 Air Conditioner

Not finding what you are looking for?
Goodman GMS90703BXA Heater Logo

Related Topics:

117 people viewed this question

Ask a Question

Usually answered in minutes!

Top Goodman Heating & Cooling Experts

Dan Webster
Dan Webster

Level 3 Expert

8220 Answers

paulcarew

Level 3 Expert

2464 Answers

Brandon Berry
Brandon Berry

Level 2 Expert

407 Answers

Are you a Goodman Heating and Cooling Expert? Answer questions, earn points and help others

Answer questions

Manuals & User Guides

Loading...